INSTALLATION OF INDOOR
ENGLISH
9
CAUTION
• Install declination of the indoor unit is very important for the drain of the duct type air condi-
tioner.
• Minimum thickness of the insulation for the connecting pipe shall be 5mm.
Front of view
• The unit must be declined to the drain hose connected when finished installation.
!
Drainage hole
U-Trap
B
C
A
≥
70 mm
B
≥
2C
C
≥
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10 mmAq
A
≥
70 mm
B
≥
40 mm
C
≥
20 mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
• Always lay the drain withdownward
inclination (1/100 to 1/50).
Prevent any upward
fl
ow or reverse
fl
ow
in any part.
• 10 mm or thicker formed thermal insulator
shall always be provided for the drain
pipe.
• Install the P-Trap
(
or U-Trap) to prevent
a water leakage caused by the blocking
ofi ntake air filter.
Applied U-Trap Dimension
CORRECT
INCORRECT
• Upward routing not
allowed
Caution for gradient of unit and drain piping
Lay the drain hose with a downward inclination so water will drain out.
1,MFL67939925,영어 2017. 7. 17. 오후 2:34 페이지 9
Drainage hole
Drainage hole
CORRECT
INCORRECT
1/100~1/50
Ceiling
Содержание ABNW12GL5S1
Страница 28: ...28 ENGLISH 1 MFL67939925 영어 2017 7 17 오후 2 34 페이지 28 ...
Страница 56: ...28 FRANÇAIS 2 MFL67939925 불어 2017 7 17 오후 2 29 페이지 28 ...
Страница 59: ... ABNW12GL5S1 1 10 ٨ ٢ 3 MFL67939925 아랍어 2017 7 17 오후 2 26 페이지 26 ا ل ع ر ب ي ة ...
Страница 74: ...1 1 1 ...
Страница 75: ... م ق د م ة ح و ل ا ل م ن ت ج ٠ ١ ً 3 MFL67939925 아랍어 2017 7 17 오후 2 26 페이지 10 ...
Страница 77: ...1 2 3 4 5 4 X 4 X 4 X 4 X 4 X 4 X 3 MFL67939925 아랍어 2017 7 17 오후 2 26 페이지 8 ٨ ...
Страница 78: ......
Страница 79: ......
Страница 84: ... ا ل ع ر ب ي ة www lg com ً ً ﺍ 3 MFL67939925 아랍어 2017 7 17 오후 2 26 페이지 1 ...