OPTIONAL OPERATION
ENGLISH
21
[Table. 1]
ABNQ54GRLA0
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
14(137)
95
41.3
100
45.4
39.7
105
49.5
44.1
38.6
110
48.5
44.2
38.9
115
49.8
44.7
42.2
120
50.5
48.1
ABNQ48GRLA0
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
85
31.5
90
36.3
29.8
95
41.3
34.5
28.4
100
45.4
39.7
33.5
27.3
105
44.1
38.6
33.1
110
44.2
38.9
115
44.7
ABNQ42GRLA0
Setting Value
Static Pressure[mmAq(Pa)]
6(59)
8(78)
10(98)
12(118)
85
31.5
90
36.3
29.8
95
41.3
34.5
28.4
100
45.4
39.7
33.5
27.3
105
44.1
38.6
33.1
110
44.2
38.9
115
44.7
ABNQ36GGLA0
Setting Value
Static Pressure[mmAq(Pa)]
4(39)
6(59)
8(78)
10(98)
100
20.8
105
23.2
19.5
110
26
21.5
115
23.5
19.1
120
26.3
21.6
125
24
19.9
130
27
22.7
135
25.9
ABNQ24GGLA0
Setting Value
Static Pressure[mmAq(Pa)]
2.5(25)
4(39)
6(59)
8(78)
10(98)
80
14.8
90
19
14.4
100
23.3
19.7
13.9
110
26.9
24.3
19.8
14.1
120
31.2
28.2
25.2
20.1
14.4
130
34.9
32.4
29.5
26.1
20.5
ABNQ18GHLA0
ABNQ21GHLA0
Setting Value
Static Pressure[mmAq(Pa)]
2.5(25)
4(39)
6(59)
8(78)
100
12.8
105
13.9
110
15.2
12.7
115
16.5
14
120
17.8
15.3
12.7
125
16.5
14
130
17.8
15.3
12.6
135
16.5
13.5
140
17.5
14.5
145
16.5
NOTE
!
1. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
2. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
* ABNQ42GRLA0 / ABNQ48GRLA0 As far as possible do not set ESP 82,83