HOW TO SET E.S.P?
ENGLISH
27
Ceiling Concealed Duct – Low static
Table 1
NOTE
!
1. The above table shows the correlation between the air rates and E.S.P.
2. Be sure to set the value refering table 1. Unexpected set value will cause mal-function.
3. Table 1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Model
Step
CMM
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
AMNW09GL1A2
AMNQ09GL1A0
ABNQ09GL1A2
LOW
5.5
69
76
83
91
101
111
MID
7
81
87
94
101
109
117
HIGH
9
97
103
108
117
124
131
Model
Step
CMM
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
AMNW12GL2A2
AMNQ12GL2A0
ABNQ12GL2A2
LOW
7
78
82
87
93
100
107
MID
8.5
87
91
94
100
108
116
HIGH
10
96
100
103
109
117
125
Model
Step
CMM
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
AMNW18GL2A2
AMNQ18GL2A0
ABNQ18GL2A2
LOW
10
96
100
103
109
117
125
MID
12.5
109
113
117
123
130
137
HIGH
15
120
124
129
134
141
147
Model
Step
CMM
Static Pressure [mmAq (Pa)]
0(0)
1(10)
2(20)
3(29)
4(39)
5(49)
Setting Value
32:01
32:02
32:03
32:04
32:05
32:06
AMNW24GL3A2
AMNQ24GL3A0
ABNQ24GL3A2
LOW
12
89
95
102
106
120
130
MID
16
102
108
115
125
131
139
HIGH
20
125
131
136
141
144
147