14
INSTALLATION
ENGLISH
Indoor Unit
Outdoor Unit
(Btu/h class)
Type
Capacity
(Btu/h
class)
36k
54k
Vertical
AHU
24k
O
O
36k
X
O
Ceiling
Concealed
Duct
(High
Static)
24k
O
O
36k
X
O
BD unit (PMBD3641)
A8UW54GFA0
[LMU540HV]
Example)
Total rated capacity index :
4Way CST
AMNW18GTQA0
[LMCN185HV]
18
VAHU
AMNW36GNJA0
[LMVN360HV]
36 x 1.3
Outdoor Unit
(Btu/h class)
Total capacity of connectable
indoor units (Btu/h)
36k
48k
54k
73k
Combination indoor units
(AMNW**GBGA0 / TYPE B)
The indoor units connectable to the outdoor
unit are shown below
NOTE
!
1. The total capacity(in Btu/h unit) of
connected indoor unit models
represents the total sum of the figures
expressed in the indoor model name.
2. Combinations in which the total capacity
of the connected indoor units exceeds
the capacity of the outdoor unit will
reduce the capacity of each indoor unit
below the rated capacity during
simultaneous operation. Therefore, if
circumstances allows, combine indoor
units within the capacity of the outdoor
unit.
3. VAHU, Ceiling Concealed Duct(High
Static) type indoor unit’s combination
calculation method as below.
Calculation method for total capacity of
connectable indoor unit to an outdoor
unit
= (Sum of all VAHU & Ceiling Concealed
Duct(High Static) type indoor units
capacity
x 1.3) + Sum of all other indoor unit’s
capacity
64.8 < 73
+
=