INSTALLATION
INSULATION, OTHERS
Insulate the joint and tubes completely.
All thermal insulation must comply with local requirement.
INDOOR UNIT
THERMAL INSULATION
After all workings are finished, check the working and operation.
• Air distribution ............. Is the air circulation good?
• Drain ............................ Is the drainage smoothly and no sweating?
• Gas leakage ................ Is the piping connection correctly?
• Wiring ......................... Is the wiring connection correctly?
• Lock-bolt ...................... Is the lock-bolt of compressor loosened?
• Insulation ..................... Is the unit fully insulated?
• Ground......................... Is the unit safely grounded?
TEST AND CHECK
Make sure that there is no clearance here.
Overlap with thermal
insulator for piping.
Thermal insulator for refrigerant pipe
(Local supply)
Thermal insulator for
piping(Local supply)
Hose clip for thermal insulator(Local supply)
Refrigerant pipe and thermal
insulator(Local supply)
Thermal insulator for refrigerant pipe
(Local supply)
Hose clip for thermal insulator
(Local supply)
Felt
Insulation
No clearance
Cabinet
Union for liquid pipe
Union for gas pipe
Checking the Drainage
1
Remove the Air Filter.
2
Check the drainage.
- Spray one or two glasses of water upon the evaporator.
- Ensure that water flows drain hose of indoor unit without any leakage.
<TYPE A>
<TYPE B/C>
<TYPE A>
<TYPE B/C>