Ceiling Concealed Duct
25
50Hz • R410A • Heat Pump
E.S.P. Setting for
Table 11-1
Static Pressure(mmAq)
Setting Value
0
2
4
6
8
Model Name
Step
CMM(CFM)
High
32(1130)
230
230
225
220
150
Mid
29(1024)
240
238
237
235
230
Low
26.5(936)
245
245
243
243
240
High
18(636)
220
205
190
50
1
Mid
16.5(583)
235
230
220
200
100
Low
14(494)
250
240
235
230
210
Note: 1. To get the desired Airflow & E.S.P combination from the table set the matching value from
the table. Value other than that in table will not give the combinations of airflow & ESP
which are mentioned in the table.
2. Table 11-1 is based at 230V. According to the fluctuation of voltage, air flow rate varies.
AB-H366GSA0
[B36AH SG0]
AB-H426GSA0
[B42AH SG0]
AB-H306GTA0
[B30AHV SG0]
AB-H366GTA0
[B36AHV SG0]
AB-H246HTA0
[B24AHV SH0]