Installation Manual
39
Connecting the Cable between Indoor Unit, Distributor Unit and Outdoor Unit
ENGLISH
60 kBtu/h class
Power cord terminal
Connecting cable terminal
Cord clamp
Cord clamp
* Make sure the rubber bushes are
Properly used in knock-out holes after
connecting main power cable.
:
1. Use connection cable NRTL(UL, ETL, CAS…) listed and stranded copper(4) THHN conductors,
sunlight (UV) resistant ROHS compliant PVC jacket 600 V direct burial listed, approved for wet
conditions. Temperature rated for –20 ℃(-4 ℉) to 90 ℃(194 ℉). And this cable should be
enclosed in conduit.
WARNING
• Be sure to comply with local and national codes while running the wire from the indoor unit to
the outdoor unit(size of wire and wiring method, etc).
• Every wire must be connected firmly.
• No wire should be allowed to touch refrigerant tubing, the compressor or any moving parts.
• The communication wirings of air conditioner should be separate and isolated from external
device’s electric wiring such as computers, elevator, radio & Television broadcasting facilities,
as well as medical imaging offices.
NOTICE
!