CONNECTING THE CABLE BETWEEN INDOOR UNIT AND OUTDOOR UNIT
ENGLISH
Connect the cable to the Indoor unit
Connect the cable to the indoor unit by connecting the wires to the terminals on the control
board individually according to the outdoor unit connection. (Ensure that the color of the wires of
the outdoor unit and the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.
The circuit diagram is not subject to change without notice.
When installing, refer to the circuit diagram behind the panel front of Indoor Unit the wiring
diagram on the Control Cover Inside Outdoor Unit.
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
CAUTION
CONNECTING THE CABLE BETWEEN INDOOR
UNIT AND OUTDOOR UNIT
The power cord connected to the outdoor unit should be complied with the following
specifications (Cable type approved by HAR or SAA).
This equipment shall be provided with a cable set complying with
the national regulation.
The power connecting cable connected to the indoor and outdoor unit
should be complied with the following specifications (This equipment
shall be provided with a cord set complying with the national
regulation).
CAUTION
Provide a circuit breaker between power source
and the unit as shown below.
CAUTION
Air
Conditioner
Main power source
Circuit Breaker
Use a circuit breaker
or time delay fuse.
GN/YL
20 mm
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm
2
H07RN-F
ø7.5 mm
GN/YL
20 mm
Capacity (kBtu/h)
18
26
30
36
40
48
54
NORMAL CROSS SECTIONAL AREA
2.5
2.5
2.5
2.5
3.5
3.5
3.5
Cable Type
H07RN-F
(mm
2
)
!
!
!