54
MPS Variable Multi Split System(50Hz, R410A)
10. Capacity Table
10.5 A2UH146FA0
[Cooling Capacity]
[Heating Capacity]
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
Combination
Capacity Index
(kBtu/h)
Outdoor
Air Temp.:
°CDB
14 16
18 19 22 24
Indoor Air Temp.: °CWB
21
2.63 0.92 2.81 0.94 2.93 0.95 3.04 0.97 3.18 0.98 3.26 1.00
24
2.59 1.01 2.77 1.03 2.89 1.04 2.99 1.06 3.14 1.08 3.21 1.09
7
29
2.50 1.16 2.67 1.18 2.79 1.20 2.88 1.22 3.02 1.24 3.09 1.25
35
2.38 1.29 2.55 1.31 2.66 1.33 2.75 1.35 2.89 1.37 2.95 1.39
41
2.26 1.38 2.42 1.40 2.52 1.42 2.61 1.45 2.73 1.47 2.80 1.48
46
2.11 1.46 2.26 1.48 2.35 1.50 2.44 1.53 2.55 1.55 2.61 1.57
21
4.03 0.99 4.31 1.01 4.49 1.02 4.65 1.04 4.87 1.06 4.99 1.07
24
3.97 1.09 4.25 1.11 4.43 1.12 4.58 1.14 4.81 1.16 4.92 1.17
7+7
29
3.82 1.25 4.10 1.27 4.27 1.29 4.42 1.31 4.63 1.33 4.74 1.35
35
3.65 1.38 3.91 1.41 4.08 1.42 4.22 1.45 4.42 1.47 4.53 1.49
41
3.46 1.48 3.70 1.50 3.86 1.52 3.99 1.55 4.19 1.57 4.28 1.59
46
3.23 1.56 3.46 1.59 3.60 1.61 3.73 1.64 3.91 1.66 4.00 1.68
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
Combination
Capacity Index
(kBtu/h)
Indoor
Air Temp.:
°CDB
-10
-5
0
6
10
15
Outdoor Air Temp.: °CWB
16
1.98 1.09 2.33 1.20 2.70 1.30 3.14 1.41 3.39 1.48 3.75 1.59
18
1.92 1.13 2.26 1.24 2.61 1.35 3.04 1.45 3.29 1.53 3.63 1.64
7
20
1.86 1.17 2.19 1.28 2.53 1.39 2.93 1.50 3.19 1.58 3.52 1.69
22
1.79 1.21 2.11 1.32 2.44 1.43 2.84 1.55 3.07 1.63 3.39 1.75
24
1.73 1.24 2.04 1.36 2.36 1.48 2.74 1.60 2.97 1.68 3.28 1.80
16
2.89 0.95 3.40 1.04 3.94 1.13 4.58 1.22 4.96 1.28 5.47 1.37
18
2.80 0.98 3.30 1.07 3.81 1.17 4.43 1.26 4.80 1.33 5.30 1.42
7+7
20
2.71 1.01 3.20 1.11 3.70 1.20 4.28 1.30 4.66 1.37 5.14 1.47
22
2.62 1.04 3.08 1.14 3.57 1.24 4.15 1.34 4.49 1.41 4.95 1.51
24
2.53 1.08 2.98 1.18 3.44 1.28 4.00 1.38 4.33 1.46 4.78 1.56
Notes:
1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0m
2. TC : Total Capacity (kW)
PI : Power Input (kW)
Notes:
1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0m
2. TC : Total Capacity (kW)
PI : Power Input (kW)
Heat Pump
Содержание A2UC146FA0
Страница 1: ...LM50 2004 E1 MPS Variable Multi Split SYSTEM Free Joint 50Hz R410A ...
Страница 3: ...2 MPS Variable Multi Split System 50Hz R410A ...
Страница 5: ...4 MPS Variable Multi Split System 50Hz R410A ...
Страница 6: ...2004 Product Data 5 Part 1 Features ...
Страница 11: ...10 MPS Variable Multi Split System 50Hz R410A ...