background image

INSTALLATION OVERVIEW

2

The following should  be always
observed for safety....................3

Installation of indoor, outdoor
unit................................................4

Flaring work and connection of
piping ...........................................7

Connecting the cable between
indoor unit and outdoor unit..10

Checking the drainage and
Forming the piping ..................12

Air purging  ...............................14

Panel Front Assembly ............16

Test running .............................17

❏ 

Installation guide map

Four type "A" screws & plastic
anchors

Connecting cable

Pipes: Gas side ....................1/2"

Liquid side .................1/4"
(Refer to page 4)

Insulation materials

Additional drain pipe
Outer Diameter......15.5mm(

5

/

8

")

Two type "B" screws

Level gauge

Screw driver

Electric drill

Hole core drill Ø50mm(1.97")

Horizontal meter

Flaring tool set

Specified torque wrenches

Liquid side - 1.8kg.m(13ft.lbs):9K,12K,18K

4.0kg.m(28.9ft.lbs):24K

Gas side - 5.5kg.m(39.8ft.lbs):9K, 12K

6.6kg.m(47.7ft.lbs):18K, 24K 

(Refer to page 9)

Spanner......................Half union

A glass of water

Screw driver

Hexagonal wrench 4mm(

5

/

32

")

Gas-leak detector

Vacuum pump

Gauge manifold

Owner's manual

Thermometer

Holder Remote Control

Installation

Requirements

Required Parts

Required Tools

Содержание 3828A30087L

Страница 1: ...en lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your finger When installing in a wall Make sure the wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support in a room Properly insulate any tubing run inside a room to prevent sweating that can cause dripping and wa...

Страница 2: ...2 Liquid side 1 4 Refer to page 4 Insulation materials Additional drain pipe Outer Diameter 15 5mm 5 8 Two type B screws Level gauge Screw driver Electric drill Hole core drill Ø50mm 1 97 Horizontal meter Flaring tool set Specified torque wrenches Liquid side 1 8kg m 13ft lbs 9K 12K 18K 4 0kg m 28 9ft lbs 24K Gas side 5 5kg m 39 8ft lbs 9K 12K 6 6kg m 47 7ft lbs 18K 24K Refer to page 9 Spanner Hal...

Страница 3: ...s not applied to the sections If the electrical part cover of the indoor unit and or the service panel of the outdoor unit are not attached securely it could result in a fire or electric shock due to dust water etc Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely The use of defective parts could cause an injury due to a fire electric shock the ...

Страница 4: ...ce animals and plants in the path of the warm air Take the air conditioner weight into account and select a place where noise and vibration are minimum Select a place so that the warm air and noise from the air conditioner do not disturb neighbors Rooftop Installations If the outdoor unit is installed on a roof structure be sure to level the unit Ensure the roof structure and anchoring method are ...

Страница 5: ... for fixing cover pipe Pull up the cover side of desired connecting direction then cover side is separated In case connecting direction is left or right path through the hole of cover side B When connecting pipe path through rear wall don t remove the hole Drain hose junction Remove the rubber stopple of desired drain direction As the following picture Insert drain hose in the handle of drain pan ...

Страница 6: ...face Refer to No 5 on this page when making a hole in the wall First Drive the two points of the upper parts by screws Leave 10mm 0 39 for hanging product Drive the lower parts after facing the hole of product with plastic anchors and fix completely the upper screws In case of nothing wrong in the matter connect the pipe and the wire Installation manual reference Horizontality IN STALLATIO N GUID ...

Страница 7: ...ing completed burr removal not possible to put them on after flaring work C Copper pipe 90 Slanted Uneven Rough Bar Copper pipe Clamp handle Red arrow mark Cone Yoke Handle Bar A Pipe Reamer Point down Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper pipe in a die in the dimension shown in the table above D Check Compare the flared work with figure below If ...

Страница 8: ...ion will not damage furniture or floors Foamed polyethylene or equivalent is recommended Connecting cable Gas side piping Liquid side piping Drain hose Loop Wrap the insulation material around the connecting portion Overlap the connection pipe insulation material and the indoor unit pipe insulation material Bind them together with vinyl tape so that there is no gap D Plastic bands Insulation mater...

Страница 9: ...wrench Outdoor unit Gas side piping Bigger diameter Liquid side piping Smaller diameter Torque wrench Outdoor unit Liquid side piping Smaller diameter Gas side piping Bigger diameter Torque wrench Pipe Size Torque GAS LIQUID 9K 1 2 5 5kg m 1 4 1 8kg m 12K 1 2 5 5kg m 1 4 1 8kg m Capacity Btu h Installation Information For right piping Good case For right piping follow the instruction below Press o...

Страница 10: ...several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes 1 shows field wiring 2 Separately wire the high and low voltage line 3 Use heat proof electrical wiring capable of withstanding temperatures up to 167 F 4 Use outdoor and waterproof connection cable rated more than 300V for the connection between indoor and outdoor unit For example Type SJO WA Be ...

Страница 11: ...it panel When connecting each power wire to the corresponding terminal follow instructions How to connect wiring to the terminals and fasten the wire tightly with the fixing screw of the terminal plate How to connect wiring to the terminals For solid core wiring or F cable 1 Cut the wire end with a wire cutter of wire cutting pliers then strip the insulation to expose the solid wire about 25mm 15 ...

Страница 12: ...ical parts Seal small openings around pipings with a gum type sealer In cases where the Outdoor unit is installed above the Indoor unit perform the following Tape the piping and connecting cable from down to up Secure the taped piping along the exterior wall Form a trap to prevent water entering the room Fix the piping onto the wall by saddle or equivalent C Seal a small opening around the pipings...

Страница 13: ...he terminals on the control board individually according to the outdoor unit connection Ensure that the color of the wires of outdoor unit and the terminal No are the same as those of indoor unit respectively Refer to Wiring diagram on page10 Be sure to refer to the wiring diagram label inside the grille and carry out the correct field wiring Wrong wiring can cause the unit to misoperate to result...

Страница 14: ... and dry nitrogen gas cylinder to this service port with charge hoses Pressurize the system to no more than 150 P S I G with dry nitrogen gas and close the cylinder valve when the gauge reading reached 150 P S I G Next test for leaks with liquid soap Lo Hi Indoor unit Outdoor unit Manifold valve Charge hose Nitrogen gas cylinder in vertical standing position Pressure gauge A B Do a leak test of al...

Страница 15: ...urely with an adjustable wrench This process is very important to prevent leakage from the system Replace the valve caps at both gas and liquid side service valves and fasten them tight This completes air purging with a vacuum pump The air conditioner is now ready to test run C D 1 Remove the caps from the 2 way and 3 way valves 2 Remove the service port cap from the 3 way valve 3 To open the 2 wa...

Страница 16: ...er assembly exactly Fix power cord in the bottom groove of cover side left A B Assemble connecting lead wire with controller and first fix the upper part of panel front then match the lower part of panel front Panel Front Connector C Drive two screws ...

Страница 17: ...rged and charge should be removed If the actual pressure are lower than shown the system is most likely undercharged and charge should be added The air conditioner is now ready for use A C B Bolt Tubing connection This is performed when the unit is to be relocated or the refrigerant circuit is serviced Pump Down means collecting all refrigerant in the outdoor unit without loss in refrigerant gas C...

Отзывы: