Indoor unit installation
1
The mounting floor should be strong and
solid enough to prevent it from vibration.
2
Drill the piping hole with 70mm diameter
hole-core drill at either the right or the left
of indoor unit. The hole should be sightly
slant to the outdoor side.
3
Insert the plastic tube through the hole.
4
Cut the extruded outside part of the plastic
tube, if necessary.
- When using knock-out hole to route
the piping, insert the plastic cover in
knock-out hole in order to prevent the
piping from damaged by sharp edge of
the hole.
Outdoor unit installation
1
Install the outdoor unit on the concrete or
any solid base securely and horizontally by
securing it with bolts (Ø12mm) and nuts.
2
If there is any vibration transmitted to the
building, mount the rubber underneath the
outdoor unit.
Refrigerant amount
Before shipment, this air conditioner is filled
with the rated amount of refrigerant including
additional amount required for air-purging,
subjected to 7.5m piping length. (The rated
amount of refrigerant is indicated on the name
plate.) But when the piping length exceeds
standard length, additional charge is required
according to the following table.
Example) 36k
In case of 15m long pipe
the amount of refrigerant to be replenished
(15-7.5) X 30 = 225g
200mm
70mm
70mm
90mm
Wall
Core Drill
Tilt
Cut if
necessary
More
than 15mm
Wall
Plastic tube
(Bushing)
INSIDE
OUTSIDE
Capacity
(Btu/h)
Standard
Piping length
Refrigerant
charge
36k
7.5m
30g/m
48K
7.5m
40g/m
ENGLISH
INSTALLATION
8
INSTALLATION