Installation
Ground wire connection
NOTE
Grounding between the battery pack and the inverter is not mandatory but
recommended.
ON
OFF
CON
NEC
TION
KIT
1. Thread the ground wire from the in-
verter through a smaller grommet and
then through the bottom of the smaller
holes.
2. Connect the ground wire to the
ground screw, and tighten it to a
torque of 4 N·m The screw type is M5.
3. Push the grommet into the hole.
Charging cables connection
ON
OFF
CON
NEC
TION
KIT
1. Make sure that the cross-sectional area
of the charging cables is 33 to 50 mm
2
.
Thread the charging cables through
each of the larger grommets and then
through each of the larger holes.
23