63D4002
11
Do not connect the heater to any air distribution duct or system.
In Canada:
The Canadian Standards Association has established different guidelines. Figure
11 shows one method, in which all combustible material in the wall is cut away to provide the
required 18
"
(450 mm) clearance for the connector. The resulting space must remain empty.
A flush mounted sheet metal cover may be used
on one side only.
If covers must be used on
both sides, each cover must be mounted on non-combustible spacers at least 1
"
(25mm) clear
of the wall. Your Lexington Forge dealer or your local building inspector can provide details of
other approved methods of passing a chimney connector through a combustible wall. In Canada,
this type of installation must conform to CAN/CSA-B365. Installation Code for Solid Fuel Burning
Appliances and Equipment.
NOTE:
Do not vent your stove into a factory-built (zero-clearance) fireplace. These appliances
and their chimneys are specifically designed as a unit for use as fireplaces. It may void the listing
or be hazardous to adapt them for any other use.
FLOOR PROTECTOR
Installation on a Concrete Floor
An appliance mounted on a concrete floor does not require floor protection.
Carpeting and any other combustible material shall not cover the floor protector.
If a combustible surface is applied to the concrete floor, a clearance must be maintained
equivalent to the area reserved for the floor protector.
See Figure 4.
Installation on a Combustible Floor
If the appliance is to be installed on a combustible floor or a combustible floor covering, it must be
installed on a non-combustible floor protector. The pad must be installed beneath the appliance
extending 18
"
(457 mm) in Canada, 16
"
(406 mm) in the U.S. on any side equipped with a door,
and 8
"
(203 mm) on all other sides. In the U.S. the pad must cover any horizontal chimney
connector runs and extend 2
"
(51 mm) beyond each side.
INSTALLATION
2”
(51 mm)
2”
(51 mm)
8”
(203 mm)
*18” (457 mm)
**16” (406 mm)
8”
(203 mm)
8”
(203 mm)
ST1011
floor protection
10/08
Wall Line
Floor Protector
Door Side of
Appliance
* Canada
** US
ST1011
Figure 4: Installation on a combustible floor