10.
CONFIGURATION OF THE PARAMETERS
Analog
Configuration of the analog outputs
DAC
- Digital to Analog Converter
It can be selected the type of the output
between :
•
0-10V
•
4-20mA
•
0-20mA
•
0-24mA
It changes the analog output of
temperature and conductivity outputs at
the same time.
By default, it shows the last loaded type.
TC
We can select the temperature
compensation type. Two possible
options here:
•
TC-NO - no compensation
•
TC-LIN - linear compensation
Conductivity High(uS/cm)
Assign the desired upper limit of the conductivity value to the upper limit of the
analog output. For example, if you want the analog output to be 20 mA, when
the measured conductivity is 200uS/cm we select the 4-20 mA output for the
DAC and enter 200 in the “Conductivity High” window, then “
Save
”.
Conductivity Low(uS/cm)
Assign the desired lower limit of the conductivity value to the lower limit of the
analog output.
In that case, if you
want to 100uS/cm corresponds to 4 mA, you
need to select the 4-20 mA output for the DAC and enter 100 in the
“Conductivity Low” window, then “
Save
”.
Temperature High(C)
Assign the desired upper limit of the
temperature
value to the upper limit of the
analog output.
For example, if you want the analog output to be 20 mA, when
the measured
temperature
is
95 C degree,
it should be
select the 4-20 mA
output for the DAC and enter
95
in the “
Temperature
High” window, then “
Save
”.
Temperature Low(C)
Assign the desired lower limit of the
temperature
value to the lower limit of the
analog output. Same operation as for the upper value, only the lower value
entered here.