WARNINGS AND CAUTIONS
:
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult a qualified electrician.
• To avoid overheating and possible damage to this device and other equipment, use only with the appropriate Advance Transformer 277V Mark 10™ Powerline electronic ballasts for
controlling the specific fluorescent lamps.
• When retrofitting Mark 10™
Powerline
dimming ballasts into fixtures that originally had Instant Start ballasts, the sockets MUST be replaced with Rapid Start sockets to allow proper
dimmer operation and prevent damage to the dimmer ballast. Refer to the instructions provided with the ballast.
• Vizia™ dimmers are not compatible with standard 3-way or 4-way switches. They must be used with compatible Vizia™ remotes for multi-location dimming.
• Use only one (1) Vizia™ dimmer in a multi-location circuit with up to 9 coordinating remotes without LEDs or up to 4 matching remotes with LEDs. The remote(s) will turn the light on
at the brightness level selected at the dimmer.
WARNINGS AND CAUTIONS
:
• Lamps must be burned in at full intensity for 100 hours prior to dimming for proper dimming performance.
• For new installations, wire a test switch before installing dimmer.
• Total minimum load must exceed 40W.
• Dimmer may feel warm to the touch during normal operation.
• Recommended minimum wall box depth is 2-1/2".
• Maximum wire length from dimmer to all installed remotes cannot exceed 300 ft (90 m).
• Disconnect power at circuit breaker or fuse when servicing, installing or removing fixture.
• Use this device only with copper or copper clad wire. With aluminum wire use only devices marked CO/ALR or CU/AL.
Single Pole (One location) or 3-Way (Multi-location)
Fluorescent Dimmer
Cat. No. VZX12-7L (Lighted)
1200VA-277VAC, 60Hz
For use with Mark 10
TM
Powerline
dimmable ballasts
INSTAllATION INSTRUCTIONS
IMPORTANT :
For 3-Way applications, note that one of the screw
terminals from the old switch being removed will usually be a different
color (Black) or labeled Common. Tag that wire with electrical tape and
identify as the common (Line or Load) in both the dimmer wall box and
remote wall box.
For non-standard wiring applications, refer
to Wire Nut and Connector Size Chart
1 - #12 w/ 1 to 3 #14, #16 or #18
2 - #12 w/ 1 or 2 #16 or #18
1 - #14 w/ 1 to 4 #16 or #18
2 - #14 w/ 1 to 3 #16 or #18
WIRE CONNECTOR / # OF COND.
COMBINATION CHART
DI-000-VZX12-02C
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
/.
/&&
• For Single-Pole Application, go to Step 4a.
• For 3-Way Matching Remote (with lEDs) Application, go to Step 4b.
WIRING DIMMER:
Connect wires per WIRING DIAGRAM as follows:
• Green or bare copper wire in wall box to Green dimmer lead.
• Line Hot wall box wire to Black dimmer lead.
• Load wall box wire to Red dimmer lead.
• Line Neutral wall box wire to White dimmer lead.
• Yellow/Red wire should have Red insulation label affixed.
NOTE:
If insulating label is not affixed to Yellow/Red dimmer lead,
use electrical tape to cover.
•
Proceed to Step 5.
3-Way Wiring with Matching Remote
(w/lEDs) Application:
Tools needed to install your Dimmer:
Slotted/Phillips Screwdriver
Electrical Tape
Pliers
Pencil
Cutters
Ruler
If installing Dimmer in a single device application, proceed with the
INSTAllING YOUR DIMMER
section. If installing Dimmer in a multi-
device application, proceed as follows:
Installing Dimmer by itself or with other devices:
Changing the color of your Dimmer:
Your Dimmer includes three color options. The Dimmer ships with the
White frame attached. To change color of frame, proceed as follows:
Push in side at
tab to release
line up tabs and
press in side to attach
INSTAllING YOUR DIMMER
NOTE:
Use check boxes when Steps are completed.
WARNING:
TO AVOID FIRE SHOCK OR DEATH; TURN
OFF POWER
at circuit breaker or fuse and test that power
is off before wiring!
Step 1
2
4
3
1
2
4
1
5
3
Single Pole
1.
Line (Hot)
2.
Neutral
3.
Ground
4.
Load
3-Way
1.
Line or Load
(see important
instruction below)
2.
Neutral
3.
Ground
4.
First Traveler – note color
5.
Second Traveler – note color.
NOTE:
For matching remote
w/LEDs installation, the
First Traveler
becomes Line Hot.
Identifying your wiring application (most common):
NOTE:
If the wiring in your wall box does not resemble any
of these configurations, consult a qualified electrician.
Step 2
Cut
(if necessary)
5/8"
(1.6 cm)
Strip Gage
(measure bare
wire here)
Preparing and connecting wires:
Pull off pre-cut insulation from dimmer leads. Make sure that
the ends of the wires from the wall box are
straight (cut if
necessary)
. Remove insulation from each wire in the wall
box as shown:
Step 3
Dimmer
Insulating
Label
Black
Primary
Side
Ballast
Hot (Black)
Black
Line
277VAC, 60Hz
Neutral (White)
Red
Yellow/Red
White
White
Green
Ground
Cat. No. VZX12-7, 277V, For use with Advance Transformer
277V Mark 10
TM
Powerline
Electronic Ballasts
Max. # Ballasts/Dimmer for
Multi-gang
Advance
Mark 10
TM
Powerline
Part No.
lamp
Single
Gang
Two
Ganged
More than
2 Gang
VEZ-2Q18-M2-LD
VEZ-1T32
VEZ-2Q26
VEZ-1T32
VEZ-1T42
VEZ-1Q18-M2-BS
VEZ-1Q18-M2-LD
VEZ-2Q18-M2-BS
VEZ-1T32
VEZ-1T42-M2-BS
VEZ-1T42-M2-LD
VEZ-2Q26
VEZ-2Q26-M2-BS
VEZ-2Q26-M2-LD
VEZ-1Q18-M2-BS
VEZ-1Q18-M2-LD
VEZ-2Q18-M2-BS
VEZ-2Q18-M2-LD
VEZ-1T42-M2-BS
VEZ-1T42-M2-LD
VEZ-2Q26-M2-BS
VEZ-2Q26-M2-LD
VEZ-1T42-M2-BS
VEZ-1T42-M2-LD
VEZ-2T42-M3-BS
CFTR32W/GX24Q
15
15
15
CFTR32W/GX24Q
30
30
30
CFTR32W/GX24Q
30
30
30
CFTR26W/GX24Q
20
20
20
CFTR26W/GX24Q
20
20
20
CFTR26W/GX24Q
39
39
39
CFTR26W/GX24Q
39
39
39
CFTR18W/GX24Q
27
27
27
CFTR18W/GX24Q
27
27
27
CFTR18W/GX24Q
54
54
54
CFTR18W/GX24Q
54
54
54
CFQ26W/G24Q
20
20
20
CFQ26W/G24Q
20
20
20
CFQ26W/G24Q
20
20
20
CFQ26W/G24Q
39
39
39
CFQ26W/G24Q
39
39
39
CFQ26W/G24Q
39
39
39
CFQ18W/G24Q
27
27
27
CFQ18W/G24Q
27
27
27
CFQ18W/G24Q
54
54
54
CFM42W/GX24Q
54
54
54
CFM32W/GX24Q
24
24
24
CFM26W/GX24Q
30
30
30
CFM26W/GX24Q
20
20
20
39
39
39
CFM18W/G24Q
Step 4a cont'd
MAXIMUM BUlB WATTAGE
Mark 10™
Powerline
dimmers are rated in Volt-Amps (VA). The maximum
bulb wattage is determined by the efficiency of the Mark 10™
Powerline
ballast. The following table shows the maximum number of ballasts that
can be connected to a single dimmer for different Mark 10™
Powerline
ballasts. Also note that the table shows maximum ballasts for multi-gang
installations.
MAXIMUM lOAD PER DIMMER FOR MUlTI-DEVICE
More than
2 Devices
1200VA (4.3A)
Two Devices
1200VA (4.3A)
Single
1200VA (4.3A)
Cat. No.
VZX12
Single Pole Wiring Application:
Insulating label:
This wire is used in 3-way installations only.
For single pole installations, do not remove
this insulating label.
1
4
2
3
Black
White
Yellow/
Red
Green
Red
Step 4a
Step 4b
NOTE:
The dimmer
must
be installed in a wall box that has a Load
connection. The matching remote
must
be installed in a wall box
with a Line Hot connection and a Neutral connection. A Neutral wire
to the matching remote needs to be added as shown.
If you are unsure about any part of these instructions, consult a
qualified electrician.
NOTE:
Maximum wire length from dimmer to all installed remotes
cannot exceed 300 ft (90 m).
4
3
5
Additional
Neutral Wire
Matching Remote
Dimmer
Black
Green
White
Red
Yellow/Red
1
2
3
1
2
5
4
Hot (Black)
Neutral (White)
Dimmer
Matching Remote (with LEDs)
Red
Yellow/
Red
Yellow/
Red
Black
Black
Black
White
Ballast
Line
277VAC, 60Hz
Green
Ground
Green
Ground
White
White
Primary
Side
MUlTI-DEVICE APPlICATION
In multi-dimmer installations, the side sections of the mounting
strap may require removal. Use pliers to carefully bend side
sections back and forth until they break off.
Typically, removal of the side sections in multi-dimmer
installations requires a reduction of the dimmer’s capacity.
However, there is no reduction necessary for this device
.
Refer to the chart for maximum load per dimmer.
Remove
all inner
side
sections
Do not
remove
outer
side
sections
Bend back and
forth to remove
side section