01h
Register Write
Range
Register description
No
-999 ÷ 9999
Measurement value (no decimal point)
02h
No
0h, A0h, 60h,
C0h, 10h,
20h
The status of the measurement;
0h
- data valid;
A0h
- top border of the measurement
range is exceeded;
60h
- bottom border of the measurement range is exceeded;
C0h
- sensor failure;
10h
- error of user characteristic;
20h
- waiting for the first measure
03h
Yes
0 ÷ 3
“Pnt ”
parameter in
“InPt”
menu (decimal point position)
0 -
“
0”
;
1 - “ 0.0”
;
2 - “ 0.00”
;
3 - “0.000”
04h
Yes
see descr.
State of the relays and alarm LED (binary format)
(1 - on, 0 - off) :
00000000 000edcba
a
- relay R1;
b
- relay R2;
c
- relay R3;
d
- relay R2;
e
- alarm LED;
If written, only
a, b, c, d
bits are important (others are ignored)
these bits allows user to control the relays via RS-485 interface
Yes
0h ÷ 1800h
State of active current output, expressed in 1/256 mA units – it means that high byte
express integer part, and low byte fractional part of desired output current.
05h
1
Yes
2CCh÷1800h
State of passive current output, expressed in 1/256 mA units – it means that high byte
express integer part, and low byte fractional part of desired output current.
Yes
0h ÷ 1600h
State of active voltage output, expressed in 1/512 V units – it means that high byte
express integer part, and low byte fractional part of desired output voltage.
06h
No
-999 ÷ 9999
Peak (drop) value (no decimal point)
08h
No
0 ÷ 50
Temperature inside device housing expressed by 1°C
10h
Yes
0 ÷ 20
11h
Yes
0 ÷ 3
“CHAr
” parameter in
“InPt”
menu (characteristic type)
0
- linear ;
1
- square;
2
- square root;
3
- user defined
12h
Yes
0 ÷ 255
“FiLt”
parameter in
“InPt”
menu (time constant in seconds)
13h
Yes
0 ÷ 3
“Pnt”
parameter in
“InPt”
menu (the copy of 03h register, decimal
point position):
0
- “ 0” ;
1
- “ 0.0” ;
2
- “ 0.00”;
3
- “0.000”
14h
Yes
-999 ÷ 9999
“Lo C”
parameter in
“InPt”
menu, no decimal point included
15h
Yes
-999 ÷ 9999
“Hi C”
parameter in
“InPt”
menu, no decimal point included
“tyPE”
parameter in
“InPt”
menu (nominal input range):
0
- 0-20 mA range;
1
- 4-20 mA range;
2
- 0-10 V range;
3
- 2-10 V range;
4
- 0-5 V range;
5
- 1-5 V range;
6
- 0-60 mV range;
7
- 0-75 mV range;
8
- 0-100 mV range;
9
- 0-150 mV range;
10
- Pt-100;
11
- Pt-500;
12
- Pt-1000
13
- thermocouple input K;
14
- thermocouple input S;
15
- thermocouple input J;
16
- thermocouple input T;
17
- thermocouple input N;
18
- thermocouple input R;
19
- thermocouple input B;
20
- thermocouple input E;
11.1. LIST OF REGISTERS
45
www. levelprosales.com
ITC 450/470
User manual
Содержание ITC 450