the height of the highest and lowest beam above the reference plane must be selected in
accordance with EN ISO 13857.
Valid for all design types: In case of access guarding applications, the start/restart
interlock function is obligatory due to the fact that only access to the danger zone, but not
the area between the protective field and the danger points is monitored.
The start/restart button for unlocking the device must be mounted in such a way that it
cannot be reached from inside the danger zone and the entire danger zone is fully visible
form its installation position.