HTU318-300…-M12 - 01

2017/02

HTU318-1200…-M12 - 01

Adjusting the switching function (NC/NO) via the teach input

The switching function of the sensor is preset as follows on delivery:

OUT 1: NO contact

The output function can be switched from NO contact (NO - normally open) to NC contact (NC - normally closed) and vice versa. 
Leuze Teach Adapter 

PA1/XTSX-M12

 can be used for this purpose. If the switching function is changed, the switching output is 

changed to the opposite state (toggled).

Resetting to factory settings

The sensor can be reset to the factory setting (

one switching point at 300 mm or 1200 mm

). 

Leuze Teach Adapter 

PA1/XTSX-M12

 can be used for this purpose.

Changeover of the switching function

1.

To change the switching function, 

connect

 the 

Teach-IN

 input to 

U

B

 for 

more than 12s

 (Leuze Teach Adapter: position "Teach-U

B

"). 

The current state of output 

OUT1

 is frozen while the adjustment is made.

2.

The 

green and yellow LEDs flash alternately at 2Hz

The switching function was changed over. 
The switching behavior corresponds to the diagram shown above.

Resetting to factory settings 

1. When switching on the supply voltage (during Power-On),

 connect the 

Teach-IN

 input to 

U

B

 for 

> 5s

 (Leuze Teach Adapter position "Teach-U

B

"). 

The 

green and yellow LEDs

 flash 

alternately and very quickly 

for a brief time.

2. Disconnect

 the 

Teach-IN

 input from 

U

B

. The sensor was reset to the factory setting: 

switching point at 300 mm or 1200 mm (1-point teach, static)

.