NOTICE
Data reset behavior
If the data reset control bit is activated, the following actions are carried out:
Ä
Deletion of results that may still be stored.
Ä
Ä
Deletion of the input data areas of all modules.
Exception: The input data of modules 60/61 is not deleted (see chapter 10.4.21 "Module 60 -
Device status and control", see chapter 10.4.22 "Module 61 - Device application status and
control").
With the status byte of result modules 21 … 27 and entry data modules 101 … 107, the two
toggle bits are not changed.
10.4.3 Module 13 – Fragmented result
PROFINET-IO module identifier
• Module ID: 1013
• Submodule ID: 1
Description
The module defines the output of fragmented results (direction: from device to control). To occupy few i/o-
data, the results may be split into several fragments with this module. The fragments can then be transmit-
ted one after another with a handshake.
These settings act on result modules 21 … 28. The presence of this module switches on fragmentation of
the result data.
Tab. 10.4:
Parameter overview module 13
Parameter
Address
Data type
Value range
Default
Unit
Explanation
Fragment
length
0
UN-
SIGNED8
1-255
0
---
The parameter defines
the maximum length of
the result information
per fragment.
Parameter length: 1 byte
Tab. 10.5:
Input data structure module 13
Input data
Address
Data type
Value range
Default
Unit
Explanation
Fragment
number
0
Byte
0-255
0
---
Current fragment num-
ber
Remaining
fragments
1
Byte
0-255
0
---
Number of fragments
which still have to be
read for a complete re-
sult.
Fragment
size
2
UN-
SIGNED8
0-255
0
---
Fragment length, al-
ways corresponds to
the configured frag-
ment length, except for
the last fragment.
Input data length: 3 bytes, consistently