PROFINET interface
76
AMS 348
i
SSI
Leuze electronic
9.9.3.2
Module 2: Static preset
PROFINET module identifier
Module-ID 1002
Submodule-ID 1
Description
With this module, a preset value can be specified. The specified preset value becomes active
in the position in which preset teaching is performed.
Notice!
In the event of a device change the preset value is retained in the PROFINET manager. The
activation of the preset value (preset teach) at the intended position must, however, be per-
formed again.
Parameter
Input data
None
Output data
Parameter
Description
Rel.
addr.
Data
type
Value
Default
Unit
CR to
module
Metr.
Inch
Preset
Preset value.
The value is accepted during a corre-
sponding teach event (see output data).
The resolution of the preset value is
independent of the resolution selected in
module 1.
0
sign
32 bit
-999999 … +999999
0
mm
in/100
2b
4d
5d
Parameter length: 4 bytes
a
Output data
Description
Rel.
addr.
Data
type
Value
Default
Unit
CR to
module
Metr.
Inch
Preset teach
Read in the preset value.
0.0
Bit
0
1 Preset teach
–
–
4d
5d
Preset reset
Preset value is deactivated.
0.1
Bit
0
1 Preset teach
–
–
4d
5d
Output data length: 1 byte
b
c