Display and control panel AMS 308i
Leuze electronic
AMS 308
i
49
TNT
35/7-2
4
V
Position value submenu
Repetition
time
The repetition time can be set to any value between 100 and
60,000ms.
Time after which another attempt is made to establish a con-
nection.
5000
TCP/IP
Server
Port
number
The port number can be set to any value between 0 and
65535.
Local port on which the AMS 308
i
accepts connection
requests from a client application (host system) as TCP
server.
1000
UDP
Activation
ON / OFF
Activates the connection-free UDP protocol which is suitable
for e.g. transferring process data to the host. UDP and TCP/
IP can be used in parallel.
For network applications with changing partners or for only
brief data transmissions, UDP is preferred as connection-
free protocol.
OFF
IP address
IP address of the host to which the data is to be transferred.
The IP address can be set to any value in ---.---.---.--- for-
mat.
Correspondingly, the host system (PC / PLC) requires the set
IP address of the AMS 308
i
and the selected port number.
By assigning these parameters, a socket is formed via which
the data can be sent and received.
---.---.---.---
Port
number
Port number of the host to which the data is to be trans-
ferred. The port number can be set to any value between 0
and 65535.
10001
Output cycle
Value input
Output cycle of data in multiples of the AMS 308
i
measure-
ment cycle of 1.7ms.
The parameter is only valid when the cyclical transmission
of the position values is selected. Cyclical transmission is
selected via the protocol.
1
Position resolu-
tion
0.01mm / 0.1mm / 1mm / 10mm / free resolution
The measurement value can be displayed in these resolu-
tions.
The value of the free resolution is determined in the "Position
value" submenu in the "Value of free resolution" parameter.
0.1mm
Velocity resolu-
tion
1mm/s / 10mm/s / 100mm/s
1mm/s
Table 8.3:
Position value submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Measurement
unit
Metric/Inch
Specifies the units of the measured distances
Metric
Table 8.2:
Ethernet submenu
Level 3
Level 4
Level 5
Level 6
Selection/configuration option
Description
Standard