Display and control panel AMS 304i
45
AMS 304
i
Leuze electronic
Position value submenu
SSI resolution
0.001 mm / 0.01 mm / 0.1 mm / 1 mm / 10 mm / free resolution
The measurement value can be displayed in these resolutions.
The value of the free resolution is determined in the "Position value"
submenu in the "Value of free resolution" parameter.
0.1 mm
Error bit
ON/OFF
This parameter determines whether an error bit is also attached to the
"number of data bits". The error bit is the LSB and is not converted in the
case of gray representation of the measurement value.
ON
Error bit function
The error bit can be set with the following status messages:
Overflow / intensity (ATT) / temperature (TMP) /laser (LSR) /
plausibility (PLB) / hardware (ERR)
In the case of multiple namings, the individual states in the error bit are
processed in an OR function.
Plausibility
(PLB)
Hardware
(ERR)
Update rate
1.7 / 0.2 ms
1,7
Clock frequency
50 - 79 kHz / 80 - 800 kHz
Selection of the clock frequency.
80 - 800 kHz
Table 8.4:
Position value submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard
Measurement
unit
Metric/Inch
Specifies the units of the measured distances.
Metric
Count direction
Positive/Negative
Positive: The measurement value begins at 0 and increases with increas-
ing distance.
Negative: The measurement value begins at 0 and decreases with
increasing distance. Negative distance values may need to be compen-
sated with an offset or preset.
Positive
Offset
Output value=measurement value+offset.
The resolution of the offset value is independent of the selected "Reso-
lution position" and is entered in mm or inch/100. The offset value is
effective immediately following entry. If the preset value is activated, this
has priority over the offset. Preset and offset are not offset against each
other.
0 mm
Preset
The preset value is accepted by means of teach pulse. The teach pulse
can be applied to a hardware input of the M 12 PWR connector. The hard-
ware input must be appropriately configured. See also configuration of
the I/Os.
0 mm
Free resolution
value
The measurement value can be resolved in increments of 1/1000 within
the 5 … 50000 value range. If, e.g., a resolution of 0.875 mm per digit
is required, the parameter is set to 875.
In the activated interface, the measurement value display must also be
set to "free resolution" ("SSI resolution" parameter).
1000
Error delay
ON / OFF
Specifies whether, in the event of an error, the position value immediately
outputs the value of the "Position value in the case of error" parameter
or the last valid position value for the configured error delay time.
ON/100 ms
Table 8.3:
SSI submenu
Level 3
Level 4
Level 5
Selection/configuration option
Description
Standard