INSTALLATION AND MAINTENANCE

 

VARMECA - 10

 

Variable speed motor or geared motor

 

GENERAL INFORMATION

 

LEROY-SOMER

 

Réf. 3195 - 4.33/d - 12.99

 

1.3.2 - Specifications and functions

 

SPECIFICATIONS

VARMECA - 10

 

Overload

150 % of In for 40s, 10 times per hour

Motor frequency variation range

- from 12 to 80Hz at constant torque *
- from 12 to 50 Hz for general applications *
- from 6 to 220 Hz - range adjustable using parameter-setting option **

(see VARMECA - 10 manual - parameter-setting)

Efficiency

97.5 % x motor efficiency

 

CONTROL

VARMECA - 10

 

Speed reference

- Analogue reference

(0V or 4mA = minimum speed)

(10V or 20mA = maximum speed)

-  0 - 10V with integrated potentiometer
-  0 - 10V with remote potentiometer option *
-  0 - 10V with external reference *
-  4 - 20mA with external reference *
-  reference with internal potentiometer (CVI - VMA option)
-  limitation of maximum speed with internal potentiometer (CVI - VMA option)

• Digital reference

-  1 to 3 preset speeds (accessible with the parameter-setting option **)

Speed regulation

Regulation of a reference with the integrated PI loop (accessible with the parameter-
setting option **)
Specifications of the PI sensor : 0 - 10V signal 

Run/Stop

• With 3-phase power supply (10 times per hour max)
• With remote volt-free contact
• With integrated Run/Stop control (CMA option)

Forward/Reverse

• With internal connection on the terminal block
• With remote volt-free contact
• With integrated Forward/Reverse/Stop control (CMA VAR option)

Stop mode

• On ramp (with volt-free contact or integrated Run/Stop control)
• Freewheel stop (by cutting the 3-phase power supply)
• Freewheel stop (with volt-free contact or integrated Run/Stop control)

(accessible with parameter-setting option **)

• On electromechanical brake (integrated control)

Ramps

• Selection of acceleration and deceleration ramps with volt-free contact : 2s or 5s

(factory setting 5s for F max 80 Hz)

• Ramps adjustable from 0 to 20s (accessible with the parameter-setting option **)

 

INDICATIONS

VARMECA - 10

 

Display

Indicator lamp
• Permanent green light : mains connected
• Flashing green light : current limit
• Permanent or flashing orange light : overload
• Flashing red light : fault, under- or overvoltage
• Permanent red light : other fault

Relay

• Speed controller fault

volt-free contact - 1A - 250V - contact open, speed controller faulty or powered
down

Analogue output

• Speed image 0 - 10V, 3mA
• 0V = zero speed
• 10V = maximum speed

* Adjust using mini DIP switch (see section 2.3)
** See VARMECA - 10 manual - Parameter-setting.

 

en

Содержание VARMECA-10

Страница 1: ...This manual is to be given to the end user VARMECA 10 Variable speed motor or geared motor 78 84 70 46 74 installation and maintenance R f 3195 4 33 d 12 99 17 en...

Страница 2: ...ontrolled by an external safety system emergency stop fault detector The VARMECA 10 motor is fitted with safety devices which in the event of a fault control stopping and thus stop the motor The motor...

Страница 3: ...rage and correct handling must be observed The climatic conditions specified in the technical manual must be observed 4 Installation The installation and cooling of equipment must comply with the spec...

Страница 4: ...al and electromagnetic phenomena 27 3 4 Description of cables and protections 27 4 COMMISSIONING 28 4 1 Standard VARMECA 10 28 4 2 VARMECA 10 with remote potentiometer option 28 5 FAULTS DIAGNOSTICS 2...

Страница 5: ...are possible 1 2 Product name 1 3 Specifications 1 3 1 Electrical data VARMECA 10 rating Rating Power kW VMA 11 25 0 25 VMA 11 37 0 37 VMA 11 55 0 55 VMA 11 75 0 75 VMA 11 90 0 9 VMA 11 110 1 1 VMA 12...

Страница 6: ...r 0 10V signal Run Stop With 3 phase power supply 10 times per hour max With remote volt free contact With integrated Run Stop control CMA option Forward Reverse With internal connection on the termin...

Страница 7: ...er supply do not require any connection Parameter setting console Provides access to the VARMECA programming see VMA 10 manual Parameter setting Parameter setting software Specifications Level Protect...

Страница 8: ...4 Reverse the control button and cable gland supports 5 Reconnect the printed circuit layer holding the control button potentiometer and replace the fastening screws 6 Replace the cover TORX 10 slot t...

Страница 9: ...emote control cables must be shielded and have a cross section between 0 22 mm2 and 1 mm2 Incorporate a bend where the cables enter the cable glands so that water cannot penetrate the terminal box Tig...

Страница 10: ...nce 0 5 k 3 Analogue speed output 0 to 10V 3mA 0V zero speed 10V maximum speed 4 0V common with terminal 6 5 Ramp selection logic input 5s terminals 5 and 6 connected 2s terminals 5 and 6 not connecte...

Страница 11: ...y Select the required ramp Set the reference using the 10 k remote potentiometer Select the required direction of rotation The motor starts 5 FAULTS DIAGNOSTICS Information relating to the status of t...

Страница 12: ...static discharges may be destroyed simply by touching them Do not leave any metal object in the connection area as this could cause a short circuit For 3kW and 4kW ratings K1 K2 and K4 can be accessed...

Страница 13: ...filter kit FLT VMA AEM906KC002 DE cover Run Stop control kit CMA AEM906KC003 DE cover only AEM906KC004 DE cover EMC filter kit FLT VMA FWD REV control CMA VAR AEM906KC005 DE cover FWD REV control kit...

Страница 14: ...s required For a run command to be taken into account the key must be held down for one second 7 3 Forward Reverse Stop control option CMA VAR As with the CMA option the keys are located on the cover...

Страница 15: ...y The brake is energised as soon as the run command is validated It is released after a stop command at the end of deceleration or on disconnection of the power supply The rectifier circuit is mounted...

Отзывы: