INSTALLATION AND MAINTENANCE

 

VARMECA - 10

 

Variable speed motor or geared motor

 

CONNECTIONS

 

LEROY-SOMER

 

Réf. 3195 - 4.33/d - 12.99

 

3.2.4 - Control terminal block

 

This is located on the side printed circuit and used for remote
control.
To open blade terminals use a flat screwdriver (maximum
width 2.5 mm).

 

Standard configuration

 

On leaving the factory, terminals 5 and 6 are connected
together (ramp 5s) as are terminals 6 and 8 (forward).

 

Optional configuration

 

It is possible to control the motor using preset speeds, PI feedback,
etc, by setting the parameters using the console or 

 

PEGASE VMA

10 option (see VARMECA - 10 manual - Parameter-Setting).

 

3.2.5 - Fault relay terminal block

3.2.6 - Connection (standard configuration)

 

• All connections and work must be carried out with
the power switched off.

 

When connecting a 10 k

 

 

 potentiometer for remote control,

use the "without control button" option. However, if you have
the standard "with control button" version, it is essential to set
mini dip switch K4 to ON.

 

3.3 - Electrical and electromagnetic 
phenomena 

The VARMECA - 10 complies with the electromagnetic
compatibility directive 89/336/EEC, modified by 92/31/EEC,
provided it is fitted with the EMC filter option.

Ref.

Specifications

1

10V, 3 mA of the 10 k

Ω 

potentiometer

2

Reference input 0 to +10V or 4-20mA
0-10V : impedance = 100 k

4-20mA : impedance = 0.5 k

3

Analogue speed output 0 to +10V, 3mA
0V = zero speed
10V = maximum speed

4

0V common with terminal 6

5

Ramp selection logic input
5s : terminals 5 and 6 connected
2s : terminals 5 and 6 not connected

6

0V common with terminal 4

7

Reverse/stop control logic input

8

Forward/stop control logic input

1 2 3 4 5 6 7 8

Ref.

Specifications

9 - 10

Volt-free contact 250V 1 A

1

2

3

4

L1

L2

L3

9

10

PE

Fault
relay

5

6

7

8

Local or external 

potentiometer 

QS : Fused isolator

KM1 : Line contactor

Standard configuration 

0 - 10V analogue output

Speed image 

Ramp selection

Reverse/Stop

Forward/Stop

VMA 10

QS KM1

3

4

3.4 - Description of cables and protections

• When using a circuit-breaker, it must be a motor circuit-breaker (curve D).
• Comply with the size of protection fuses.
• The cable size may vary according to legislation applicable in the country, which will take precedence over the 

values given in the table below without exception.

• These tables should never be used instead of current standards.

Note : The mains current value is a typical value which depends on the source impedance. The higher the impedance, the lower 
the current.

VARMECA rating

Power (kW)

3-phase mains, 400V -10 % to 440V +10 %

Current (A)

gI fuses (A)

Cables (mm

2

)

11 - 25

0.25

1.4

3

1.5

11 - 37

0.37

1.7

3

1.5

11 - 55

0.55

2.2

3

1.5

11 - 75

0.75

3

6

1.5

11 - 90

0.9

3.5

6

1.5

11 - 110

1.1

4.1

6

1.5

12 - 150

1.5

5.3

10

1.5

12 - 180

1.8

6.2

10

2.5

12 - 220

2.2

7.7

12

2.5

13 - 220

2.2

7.7

12

2.5

13 - 300

3

8.9

16

2.5

13 - 400

4

10

16

2.5

14 - 400

4

10

16

2.5

14 - 550

5.5

13

16

2.5

14 - 750

7.5

16

20

4

en

Содержание VARMECA-10

Страница 1: ...This manual is to be given to the end user VARMECA 10 Variable speed motor or geared motor 78 84 70 46 74 installation and maintenance R f 3195 4 33 d 12 99 17 en...

Страница 2: ...ontrolled by an external safety system emergency stop fault detector The VARMECA 10 motor is fitted with safety devices which in the event of a fault control stopping and thus stop the motor The motor...

Страница 3: ...rage and correct handling must be observed The climatic conditions specified in the technical manual must be observed 4 Installation The installation and cooling of equipment must comply with the spec...

Страница 4: ...al and electromagnetic phenomena 27 3 4 Description of cables and protections 27 4 COMMISSIONING 28 4 1 Standard VARMECA 10 28 4 2 VARMECA 10 with remote potentiometer option 28 5 FAULTS DIAGNOSTICS 2...

Страница 5: ...are possible 1 2 Product name 1 3 Specifications 1 3 1 Electrical data VARMECA 10 rating Rating Power kW VMA 11 25 0 25 VMA 11 37 0 37 VMA 11 55 0 55 VMA 11 75 0 75 VMA 11 90 0 9 VMA 11 110 1 1 VMA 12...

Страница 6: ...r 0 10V signal Run Stop With 3 phase power supply 10 times per hour max With remote volt free contact With integrated Run Stop control CMA option Forward Reverse With internal connection on the termin...

Страница 7: ...er supply do not require any connection Parameter setting console Provides access to the VARMECA programming see VMA 10 manual Parameter setting Parameter setting software Specifications Level Protect...

Страница 8: ...4 Reverse the control button and cable gland supports 5 Reconnect the printed circuit layer holding the control button potentiometer and replace the fastening screws 6 Replace the cover TORX 10 slot t...

Страница 9: ...emote control cables must be shielded and have a cross section between 0 22 mm2 and 1 mm2 Incorporate a bend where the cables enter the cable glands so that water cannot penetrate the terminal box Tig...

Страница 10: ...nce 0 5 k 3 Analogue speed output 0 to 10V 3mA 0V zero speed 10V maximum speed 4 0V common with terminal 6 5 Ramp selection logic input 5s terminals 5 and 6 connected 2s terminals 5 and 6 not connecte...

Страница 11: ...y Select the required ramp Set the reference using the 10 k remote potentiometer Select the required direction of rotation The motor starts 5 FAULTS DIAGNOSTICS Information relating to the status of t...

Страница 12: ...static discharges may be destroyed simply by touching them Do not leave any metal object in the connection area as this could cause a short circuit For 3kW and 4kW ratings K1 K2 and K4 can be accessed...

Страница 13: ...filter kit FLT VMA AEM906KC002 DE cover Run Stop control kit CMA AEM906KC003 DE cover only AEM906KC004 DE cover EMC filter kit FLT VMA FWD REV control CMA VAR AEM906KC005 DE cover FWD REV control kit...

Страница 14: ...s required For a run command to be taken into account the key must be held down for one second 7 3 Forward Reverse Stop control option CMA VAR As with the CMA option the keys are located on the cover...

Страница 15: ...y The brake is energised as soon as the run command is validated It is released after a stop command at the end of deceleration or on disconnection of the power supply The rectifier circuit is mounted...

Отзывы: