LEROY-SOMER
4946 - 2013.07 / a
POWERDRIVE MD2CS
39
en
InstallatIon and maIntenance
Chassis-mounted variable speed drive
PaRameteR-settInG InteRFace and oPtIons
5.4 - RFI filters
5.4.1 - General
The use of RFI filters contributes to
a reduction in the emission levels of
radio-frequency signals (see §4.6).
Depending on the drive used, install the RFI filter recommended
in the table below between the mains and the drive input.
The cable length does not exceed 1m, the RFI filter must be
integrated on a backplate connected to the earth.
Rating
RFI filter
Reference
Irated at
40°C (A)
Leakage
current
(mA)
Losses
(W)
60t to 100t
FN 3359 HV-180
197
<6
34
120t and 150t
FN 3359 HV-250
250
<6
49
270tH
FN 3359 HV-320
350
<6
19
180t and 220t
FN 3359 HV-400
438
<6
29
340tH
270t to 400t
FN 3359 HV-600
657
<6
44
400tH to 500tH
470t
FN 3359 HV-1000
1095
<6
60
CAUTION:
The specific design of these filters makes it possible
to connect to IT power supplies. The installer should,
however, ensure that insulation supervision systems
dedicated to these installations are suitable for
monitoring electrical equipment that may contain
electronic variable speed drives.
5.4.2 - Weight and dimensions
• FN 3359 HV-180 and FN 3359 HV-250
L
L1
L1
H
H1
Ø1
M
P
type
dimensions (mm)
Weight
(kg)
l
l1
H
H1
d
Ø1
m
Fn 3359 HV-180 360
120
210
185
120
12
m10
6.5
Fn 3359 HV-250 360
120
230
205
125
12
m10
7
• FN 3359 HV-320 to FN 3359 HV-2500
L
P
L1
L1
H
H1
Ø1
M
type
dimensions (mm)
Weight
(kg)
l
l1
H
H1
d
Ø1
m
Fn 3359 HV-320
386
120
260
235 115 12
m12
10.5
Fn 3359 HV-400
386
120
260
235 115 12
m12
10.5
Fn 3359 HV-600
386
120
260
235 135 12
m12
11
Fn 3359 HV-1000 456
145
280
255 170 12
m12
18