CDC - START
console
35
Remarks
Set the rated current of the motor being controlled using the second set of parameters.
This is expressed as a % of the rated current set in menu 3 (initialisation of Softstarter).
With FR - START option only.
ON : The acceleration phase is automatically preceded by DC injection used to
immobilise the motor.
If braking before acceleration is enabled.
Set the braking level and the maximum duration of the DC injection.
If ON : The acceleration phase is preceded by a kickstart.
If kickstart is enabled :
Set the duration of the kickstart pulse (the number of half-waves).
Selects the type of acceleration ramp.
Note : The speed ramp is only available with the RV - START option.
If CURRENT RAMP
: Set the ramp parameters.
PEDESTAL
: Minimum current required to turn the load as soon as the start command
is given.
I LIMIT
: Maximum current supplied by the STV 2313. This must be sufficient to
enable starting under the most severe load conditions.
RAMP TIME
: Time taken to ramp up from the pedestal current to the current limit.
Does not represent the start time but how progressive it will be.
If SPEED RAMP: Set the ramp parameters.
I LIMIT
: Maximum current supplied by the STV 2313. This must be sufficient to
enable starting under the most severe load conditions.
ACCEL. TIME
: Acceleration time, which will remain constant whatever the load.
Attention : All current values are expressed as a % of the rated current In2.
Page: 35