background image

Small Valve

Repair Kit 1/M20 
(Packings & Gaskets)

Repair Kit R/M20 TM-20 
(Rebuilding Kit) or M20-
1-8B Bridge Assembly

Repair Kit R/M20 
(Rebuilding Kit) or M20-
G2 Thermostat Group

Repair Kit 4/M20 
(Checkstop Kit) 

Large Valve

Repair Kit  1/125Y

Repair Kit  R/125

Repair Kit R/125 or TGM-
125

Repair Kit  2/50Y

1. Leak at stem
2. Leak between valve cover and base.

3. Valve delivers either all hot or all cold 

water, or will not mix consistently.

4. After cleaning or replacing port 

sleeve/bridge assembly, valve performance 
is not consistent.

5. Hot water by-pass into cold line (or cold into 

hot).

6. Supplies cannot be shut off completely. 

Supplies leak at checkstop bonnets.

PACKING & GASKETS

PORT SLEEVE/BRIDGE 
ASSEMBLY

THERMOSTAT GROUP

CHECKSTOPS

TROUBLESHOOTING INSTRUCTIIONS

Note: Provide valve serial number when ordering parts for each valve!

See pages 6 & 7 for parts Breakdowns

5

INSTRUCTIONS FOR SERVICING 

SMALLER TM1520A VALVE

1.

Remove screw and pointer.

2.

Loosen LTR set screw.

3.

Turn off hot and cold supplies at screwdriver checkstops. Remove
M20-2C(CP) cover screws to release cover and thermostatic 
control assembly.

4.

To remove bridge assembly, M20-1-8B, remove pointer rod nut 
(MU-10B) and pull bridge assembly off control rod. 

5.

To clean, submerge bridge in clean water or non-corrosive 
cleaning solution. 

DO NOT USE ABRASIVES! 

Be certain 

thimble moves freely on the port sleeve. Note! Driving stud 
(M20-14B) must engage slot in  thimble when reassembling.

6.

To clean thermostat coil, remove retaining ring and stop, loosen
gland nut. Push rod through cover. Be careful not to pull coil out 
of shape. 

7.

Clean with a non-corrosive cleaning solution. 

DO NOT USE 

ABRASIVES!

INSTRUCTIONS FOR SERVICING 

LARGER TM1520A VALVE

1.

Loosen LTR set screw.

2.

Remove screw, snap cap, and pointer.

3.

Turn off hot and cold supplies at screwdriver checkstops. Remove
cover screws to release cover and thermostat group.

4.

To clean, port sleeve assembly (the thimble must slide freely on
the port sleeve): unscrew the check nut as far as it will go, then 
screw the port sleeve nut into base. The port sleeve and thimble 
may then be lifted out.

5.

To clean thermostat coil, remove coil sleeve stud and take off 
thermostat group.

6.

Clean with a non-corrosive cleaning solution. 

DO NOT USE 

ABRASIVES!

7.

When reassembling, make sure driving ball of thermostat group 
engages the ball socket of the port sleeve assembly. 

THERMOSTAT

GROUP

POINTER

DRIVING

BALL

PACKING

SOCKET

BALL

FLANGE

NUT

CHECK

THIMBLE

PORT
SLEEVE

PORT
SLEEVE

NUT

TM-1520A INSTRUCTIONS

GASKET

COVER

M20-3C

POINTER

CONTROL ASSEMBLY

THERMOSTATIC

TM20-1-12B

POINTER SCREW

M20-2C
COVER

SCREWS

LTR SET SCREW

ADJUSTING SCREW

TEMPERATURE

POINTER ROD NUT

MU-10B

M20-14B

STUD

DRIVING

PORT SLEEVE

BRIDGE ASSY

M20-1-8B

M20-5B

P.S. HOLDER NUT

THIMBLE

Содержание MEGATRON 7N

Страница 1: ...r 2 System should be installed at a location where it can easily be cleaned adjusted or repaired 3 System supplies must be connected as shown Hot left Cold right Exercise caution when soldering Maximum Operating Pressure 125PSI 860 KPA for Hot and Cold Water CAUTION All thermostatic water mixing valves have limitations They will not provide the desired accuracy outside of their flow capacity range...

Страница 2: ...est this temperature by holding a thermometer under the flow of water to be certain it is as desired LIMIT STOP MUST BE RESET AND RECHECKED EACH TIME HANDLE IS REMOVED POINTER SET SCREW SNAP CAP LTR C H THERMOSTATIC LEONARD STOP SCREW IMPORTANT ALL MIXING VALVES MUST BE SET AT THE SAME OPERATING TEMPERATURE SEE PAGES 6 7 FOR COMPLETE PARTS BREAKDOWN Check for significant variations in outlet flow ...

Страница 3: ...e piped according to a Leonard Required Piping Method 5 see page 4 2 Make sure full hot and cold supplies to this assembly are operating The temperature of the hot water source must be properly set and maintained 3 The circulator if used must be turned OFF before setup 4 Turn on enough fixtures for a flow of at least 30 GPM 114 l min downstream from this system Make sure each fixture is set to del...

Страница 4: ... 8 ETC UNTIL DESIRED TEMPERATURE IS ACHIEVED REMEMBER THIS IS A CONTROL DEVICE WHICH MUST BE CLEANED AND MAINTAINED ON A REGULAR BASIS SEE MAINTENANCE GUIDE AND RECORD MGR 1000 4 LEONARD VALVE CO CRANSTON RI USA TYP TM 20 40 F 0 140 30 100 20 60 LE O NARD 10 C 0 10 50 120 40 60 80 LEONARD VALVE CO CRANSTON RI USA TYP TM ISOLATION VALVE VALVE CHECK SYSTEM FIXTURES HOT WATER SOURCE COLD SUPPLY HEAT ...

Страница 5: ...e cleaning solution DO NOT USE ABRASIVES Be certain thimble moves freely on the port sleeve Note Driving stud M20 14B must engage slot in thimble when reassembling 6 To clean thermostat coil remove retaining ring and stop loosen gland nut Push rod through cover Be careful not to pull coil out of shape 7 Clean with a non corrosive cleaning solution DO NOT USE ABRASIVES INSTRUCTIONS FOR SERVICING LA...

Страница 6: ...ARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP ON EACH VALVE SEE PAGE 2 REPAIR KITS 6 04 125 SPRING LOWER STEM PACKING SWIVEL SWIVEL NUT 010 TM 02 BONNET STRAINER CAP 06 014 CAP PACKING 013 MU 5A SCREEN 1529 UPPER STEM 03 05 BONNET PACKING YELLOW O RING 09 125 TM21 125 TM21 125 2 EA 03 LOWER STEM PACKING COIL SLEEVE TM 8 STUD 03 PACKING LOWER STEM 2 EA 014 CAP PACKING CAP PACKING SPRING 1...

Страница 7: ...ACKING SPRING M20 9A M20 6A M20 3C COVER GASKET 2 EACH BONNET PKG MU 4C GLAND PKG 2 EACH 2 EACH M20 3A 2 EACH M20 9A SPRING GASKET COVER M20 3C BONNET PKG CONTROL ASSEMBLY M20 3A THERMOSTATIC M20 1 12B 2 EACH M20 6B HOLDER NUT O RING 2 EACH MU 5A O RING REPAIR KIT 2 M20 PORT SLEEVE KIT M20 G1 PORT SLEEVE ASSY HOLDER NUT M20 6B 0 RING 2 EACH 2 EACH M20 3B P S PACKING REMEMBER THIS IS A CONTROL DEVI...

Страница 8: ... REGULAR BASIS SEE MAINTENANCE GUIDE AND RECORD NOTE AFTER INSTALLING NEW PARTS IT WILL BE NECESSARY TO RESET THE ADJUSTABLE HIGH TEMPERATURE LIMIT STOP ON EACH VALVE SEE PAGE 2 CHECKSTOP PARTS REPAIR KITS MU 4A RF MU 5A UPPER CHECKSTOPS STEM PKG M20 3A BONNET PACKING AND PACKING UPPER STEM CHECK SPRING M20 6A LOWER STEM PACKING M20 9A CHECK BONNET M20 2A RF 8 TM1520A SMALL VALVE PARTS DRIVING STU...

Страница 9: ...onard will at its option repair or replace any product or part thereof which shall be returned freight prepaid to the Leonard factory and determined by Leonard to be defective in materials or workmanship Leonard provides no warranty express or implied which extends beyond the description contained herein LEONARD SPECIFICALLY DISCLAIMS ANY AND ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR OF FITNESS...

Отзывы: