LMS
Operating
Manual
Page
5
Alarm
Conditions
Temperature
Alarms
If the readings are within the alarm limits, the STATUS LED will blink green.
When the temperature reading meets or exceed the temperature limits the STATUS LED will
blink red.
After the probe’s alarm delay time is exceeded the unit will blink the ALARM LED and beep the
buzzer.
The user can MUTE the buzzer by tapping the MUTE/MENU button. The unit will reduce the
audible signal from a loud beep, to a quieter and less frequent chirp. It will remain muted until
MUTE time expires or a different probe goes into alarm.
Once the Alarm state has been signaled the unit will wait the appropriate Relay Delay(s) time
before tripping the appropriate Relay(s). Units with individual channel relays, have individual
Relay Delay times. Units with a single relay have one Relay Delay time that applies to any
alarm condition.
Limit Parameters
1 Low, 1 High, 2 Low, 2 High, 3 Low, 3 High, 4 Low, 4 High
Time Parameters
1AlarmDelay, 2AlarmDelay, 3AlarmDelay, 4AlarmDelay
Single Relay Units
RelayDelay
Individual Channel Relays
1RelayDelay, 2RelayDelay, 3RelayDelay, 4RelayDelay
Low
/
High
Alarm
Limits
For a quick view the Low and High Alarm Limits tap the DOWN ARROW.
1
AlarmLow 2.0’C
AlarmHigh 8.0’C
2
AlarmLow 2.0’C
AlarmHigh 8.0’C
3
AlarmLow 2.0’C
AlarmHigh 8.0’C
4
AlarmLow -40’C
AlarmHigh -20’C
Min/Max
Readings
To view the Min/Max readings since power up or user commanded reset, tap the UP ARROW.
1
ActualMin 3.1’C
ActualMax 6.8’C
2
ActualMin 3.6’C
ActualMax 6.6’C
3
ActualMin 3.0’C
ActualMax 7.2’C
4
ActualMin -38’C
ActualMax -32’C