6.3
Initial switch-on
Establishing communication
• To establish communication, the inverter drive must be supplied with voltage.
• POWERLINK communication requires voltage supply of the communication unit.
If this is requirement is not met, the "CE04: MCI communication error" error message (error No.
01.0127.00002) is output. The error must be reset in the Inverter Drive, so that POWERLINK
communication can be established.
• The external voltage supply serves to keep up POWERLINK communication in the event of a
main supply failure.
• Addressing can be carried out manually via DIP switches or codes in the »EASY Starter«/
»Engineer«.
Node address (node ID) setting