Address
Name / setting range / [default setting]
Info
0x2947:016
Inverter characteristic: Value y16
0.00 ... [0.00] ... 20.00 V
0x2947:017
Inverter characteristic: Value y17
0.00 ... [0.00] ... 20.00 V
In the event of an error
If an error occurs during the procedure or the pulse inhibit gets active (e.g. due to short-time
undervoltage), the procedure is terminated with inverter disable without the settings being
changed.
13.6.3.2
Extended settings for identification
For determining the characteristic, the current controller is automatically parameterised at
the start of the identification process. In case of motors with a very low stator leakage induc-
tance (< 1 mH), the automatic parameterisation can fail and the actual identification process
is aborted with an error message such as "short circuit".
•
For this case, it is possible to set the current controller manually via the
0x2942
parameter.
•
The
parameter serves to select whether the current controller should be cal-
culated automatically or the values in
0x2942
are effective.
Parameter
Address
Name / setting range / [default setting]
Info
0x2DE0:001
Current controller identification settings
Whether the current controller shall be adapted automatically for the
identification or set manually, is selected via:
•
•
(Reset time)
0 Automatisch
1 Manuell (0x2942)
0x2DE0:003
Resolver - position detection dynamics
20 ... [100] ... 100 %
Setting of the dynamics for the resolver evaluation.
•
100% ≡ max. dynamics
•
<100% ≡ reduced dynamics
0x2DE0:004
Resolver - 8 kHz safety signal
Usually ,the Der 8-kHz carrier frequency is only activated for the safety
version. This parameter can also be used to switch it on and off.
0 Automatisch durch Gerätetyp
1 Ein
2 Aus
0x2DE0:007
Use measured voltage
Activation of voltage measurement.
Only for devices for which voltage measurement is possible.
0 Aus
1 Ein
13.6.3.3
Load standard inverter characteristic
If none or only one faulty inverter characteristic could be determined, a device-typical stand-
ard inverter characteristic can be loaded.
How to load the standard inverter characteristic:
1
.
Axis commands: load standard-Lh saturation characteristic
= start 1.
2
.
After completing the procedure, save the inverter characteristic set in in the inverter.
The »EASY Starter« serves to save the parameter setting of the inverter as parameter file
(*.gdc).
Parameter
Address
Name / setting range / [default setting]
Info
0x2822:022
Axis commands: Load default inverter characteristic
Parameters for interaction with engineering tools.
0 Off/Ready
Obtain Hiperface information from the encoder for application feedback.
1 On/Start
2 In process
3 Action cancelled
4 No access
5 No access (controller inhibit)
Configuring the motor control
Options for optimising the control loops
Inverter characteristic
262
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......