Equation for calculating the reset time of the asynchronous motor
s ×
×
t =
»
s
ss
n
s
s
L
2 L
R
R
Parameter
Symbol
Description
Dimension unit
V
p
Current controller gain
V/A
-
σ
Leakage
-
L
s
Motor stator inductance
H
L
ss
Motor stator leakage inductance
H
-
T
Dead time
Equivalent time constant for the
analog detection and scanning =
0.00034 s
s
T
n
Current controller reset time
s
R
s
Motor stator resistance (value at
20° C)
Ω
Parameter
Address
Name / setting range / [default setting]
Info
0x2941
Current controller feedforward control
Activate/deactivate feedforward control.
Since the actuation of the current controller is known, they can be pre-
controlled to increase the actuations of the current controller.
Note!
For a feedforward control, the Motor equivalent circuit diagram data
must be known. If only estimated values are available, we recommend
you not to activate the feedforward control.
0 Disable
1 Enable
0x2942:001
Current controller parameters: Gain
0.00 ... [148.21] ... 750.00 V/A
Gain factor Vp of the current controller.
0x2942:002
Current controller parameters: Reset time
0.01 ... [3.77] ... 2000.00 ms
Reset time Ti of the current controller.
0x2943
Current setpoint filter time
0.00 ... [0.00] ... 10.00 ms
Setting of the setpoint current filter time.
Configuring the motor control
Options for optimising the control loops
Motor control settings
268
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......