12.1.1
General settings
This chapter provides information on general settings of feedback systems for the motor con-
trol.
Pressing the Select resolver or Select encoder button displays a list of resolvers or encoders.
If the displayed list contains the feedback system used, the data is applied automatically.
Otherwise, you must enter the data of the feedback system manually.
Monitoring of the encoder cable for wire breakage
The resolver or encoder cable can be monitored for wire breakage in the default settings of
parameter
DANGER!
When the encoder / resolver is used as a motor encoder, safe motor operation is not possible
in the event of an error.
Destruction of system parts
▶
Fault should always be used as a response for resolver/encoder wire breakage monitoring.
▶
To prevent interference injections when using an encoder, only use shielded motor and
encoder cables.
Wire breakage monitoring trips in the following cases:
•
Resolver
•
Wire breakage in the encoder cable
•
When the resolver impedance is too great
•
In the event of interference injections (EMC interference)
•
Encoder
•
Wire breakage in the encoder cable
Sensitivity of wire breakage monitoring
The sensitivity of wire breakage monitoring can be set as a percentage using the
parameter.
Reducing the monitoring sensitivity is advantageous in environments that are severely affec-
ted by EMC problems.
If the sensitivity is not reduced (100 %), the software response time of monitor-
ing in case of an encoder is approx. 3.5 ms and in case of a resolver 0.3 ms.
Halving the sensitivity means doubling the response time.
NOTICE
A reduced sensitivity delays the response in case of wire breakage!
Destruction of system parts by reduced sensitivity of the open-circuit monitoring.
▶
Increase the sensitivity to reduce the monitoring response time.
Parameter
Address
Name / setting range / [default setting]
Info
0x2C45
Encoder-error response
Selection of the response to the triggering of the encoder signal loss
monitoring.
Only active when used as:
•
Feedback system for motor control, when set
Associated error code:
•
29443 | 0x7303 - RANLI_CIMES_1000_20870
0 No response
1 Fault > CiA402
2 Warning
Configuring the feedback system
Configure feedback system for motor control
General settings
201
Содержание i950 Series
Страница 1: ...Inverters i950 servo inverters Commissioning EN ...
Страница 2: ......
Страница 312: ...15 Configure engineering port The given path leads you to the engineering port Configure engineering port 312 ...
Страница 397: ...19 Safety functions Supported safety functions for Basic Safety STO 4Safe Torque Off STO 398 Safety functions 397 ...
Страница 497: ......
Страница 498: ......
Страница 499: ......