Technical data
Rated data
l
35
EDKZNXXXX−002 DE/EN/FR 3.0
4.2
Rated data
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
LN
[V]
U
LN
[V]
f [Hz]
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
480
432 − 0 % ... 528 + 0 %
45 ... 65
Voltage
Frequency
Current [A]
Number of
phases
Type
[V]
[Hz]
up to +40 °C
up to +55 °C
EZN3x0110H030
400/480
50/60
30
18.75
3
EZN3x0080H042
400/480
50/60
42
26.25
3
EZN3x0055H060
400/480
50/60
60
37.50
3
EZN3x0037H090
400/480
50/60
90
56.25
3
EZN3x0030H110
400/480
50/60
110
68.75
3
Temperature in the control cabinet
up to 35 °C: 130 A
Power loss
Inductance
Voltage drop
P
loss
[W]
L [mH]
D
U [V]
EZN3A0110H030
EZN3B0110H030
110
135
1.10
10
EZN3A0080H042
EZN3B0080H042
144
180
0.80
10
EZN3A0055H060
EZN3B0055H060
160
155
0.55
10
EZN3A0037H090
EZN3B0037H090
170
160
0.37
10
EZN3A0030H110
EZN3B0030H110
220
220
0.30
10