Parameter setting
7-10
BA9300SU EN 2.1
7.2.2
Change parameters
Tip!
The parameter set changed must be saved, if you do not want to loose the modifications after mains
disconnection (see chapter 7.2.3).
Basic procedure
1. Change to the code level from the menus using the arrow keys
?
,
+
,
*
or
change to the
code level. ” Code” is displayed.
2. With
?
or
+
select code or subcode.
3. Change to the parameter level using PRG.” Para” is displayed.
4. With
*
or
move the cursor (small, black bar) under the number to be changed.
5. With
?
or
+
change number.
6. Repeat 4. and 5. to change other numbers, if ncessary.
7. Accept parameters. The way the controller accepts the modified parameters is shown in the
LCD display in front of the parameter:
Display in front of the parameter
Controller uses the new value
Immediately during the change
SH+ PRG
After pressing SH+ PRG. Acknowledgement: ok in the display
SH+ PRG
Press STOP to inhibit the controller.
Press SHIFT + PRG. Acknowledgement: ok in the display
Press RUN to enable the controller
8. Press PRG twice to go to the code level. ” Code” is displayed.