13
Parameter reference
13.2
Parameters relevant for PROFINET communication
84
Lenze · Inverter Drive 8400 motec (PROFINET® option) · DMS 5.0 EN · 02/2019 · TD23
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13887
C13899
C13900
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
d
= 29C0
h
With this code, the transmission of alarm messages to the IO controller can be suppressed.
By setting the corresponding bit to TRUE, errors of a specific type can be suppressed systematically. In addition, all
errors are entered in the logbook.
• A change can only be effective immediately if no error number with the error type selected here is active in
C00165
.
Value is bit-coded:
Info
Bit 0 Error
Bit 1 Fault
Bit 2 Quick stop by trouble
Bit 3 Warning Locked
Bit 4 Warning
Bit 5 Information
Starting from SW version 3.00.
Bit 6 Reserved
Bit 7 Connection to 8400 lost
Starting from SW version 3.00.
Error message:
PROFINET: Exist. conn. to 8400 lost
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13899 | Station name
Data type: VISIBLE_STRING
Index: 10676
d
= 29B4
h
The name with a max. length of 240 characters is distributed to the subindices. The name can be entered starting
with subindex 1. The following unused subindices are not relevant.
• The station name must be assigned in accordance with the PROFINET specification. In the standard setting a
deleted name is displayed. The name is also deleted if the "Reset to factory defaults" command is executed by an
IO supervisor or an I/O controller.
• A change of the station name will only become effective by switching the mains of the inverter.
Subcodes
Lenze setting
Info
C13899/1
1st ... 30th character
C13899/2
31th ... 60th character
C13899/3
61th ... 90th character
C13899/4
91th ... 120th character
C13899/5
121th ... 150th character
C13899/6
151th ... 180th character
C13899/7
181th ... 210th character
C13899/8
211th ... 240th character
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT
Parameter | Name:
C13900 | Firmware Product Type
Data type: VISIBLE_STRING
Index: 10675
d
= 29B3
h
The code contains a string with a length of 8 characters. The identification code "E84DGFCR" is output.
Read access
Write access
CINH
PLC-STOP
No transfer
PDO_MAP_RX
PDO_MAP_TX
COM
MOT