Troubleshooting and fault elimination

Maloperation of the drive

9

l

EDK82MVXXX EN 1.0

3

Troubleshooting and fault elimination

3.1

Maloperation of the drive

Fault

Cause

Remedy

Motor does not

rotate

DC-bus voltage too low
(Red LED is blinking every 0.4 s;
keypad display

LU

)

Check mains voltage

Controller inhibited
(Green LED is blinking, keypad display:

c

)

Remove the controller inhibit, controller inhibit can be set
through several sources

Automatic start inhibited (C0142 = 0 or 2)

LOW-HIGH edge at X3/28
If necessary, correct start condition (C0142)

DC injection brake active (DCB)

Deactivate DC-injection brake

Mechanical motor brake is not released

Manual or electrical release of mechanical motor brake

Quick stop (QSP) active (keypad display:

c

)

Remove quick stop

Setpoint = 0

Setpoint selection

JOG setpoint activated and JOG frequency = 0

JOG setpoint selection (C0037 ... C0039)

Active fault

Eliminate fault

Wrong parameter set active

Change to correct parameter set via terminal

Control mode C0014 = -4-, -5-, but no motor parameter identification

Motor parameter identification (C0148)

Under C0410 several functions, which exclude each other, are assigned to the
same signal source.

Correct configuration in C0410

Use internal voltage source X3/20 for function modules Standard-I/O, INTERBUS,
PROFIBUS-DP or LECOM-B (RS485):
Bridge between X3/7 and X3/39 is missing

Jumper terminals

Motor does not

Defective motor cable

Check motor cable

Motor does not

rotate smoothly

Maximum current too low (C0022, C0023)

Adaptation to application

rotate smoothly

Motor underexcited or overexcited

Check parameter setting (C0015, C0016, C0014)

C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not adapted to
the motor data

Manual adaptation or identification of motor parameters
(C0148)

Current

Setting of C0016 too high

Correct setting

Current

consumption of

Setting of C0015 too low

Correct setting

consumption of

motor too high

C0084, C0087, C0088, C0089, C0090, C0091 and/or C0092 are not adapted to
the motor data

Manual adaptation or identification of motor parameters
(C0148)

Motor rotates,

setpoints are

“0”

With the function

j

of the keypad a setpoint has been selected.

Set the setpoint to ”0” by C0140 = 0

Motor

parameter

identification

Motor too small compared with rated power

identification

stops with error

LP1

DC brake active via terminal

Unacceptable

drive response

with vector

control

various

Vector control optimisation

efesotomasyon.com - Lenze

Show/Hide Bookmarks

Содержание E82MV Series

Страница 1: ...Information for the operator of the machine system EDK82MVXXX N Global Drive 8200 motec Frequency inverter 0 25 7 5 kW N efesotomasyon com Lenze Show Hide Bookmarks...

Страница 2: ...o not change the content you are allowed to use the information in this documentation for your purposes without contacting Lenze The information necessary for the project planning of a machine system...

Страница 3: ...50178 apply 4 Installation The controllers must be installed and cooled according to the regulations given in the corresponding Instructions Ensure careful handling and avoid mechanical overload Do n...

Страница 4: ...tools to mount or remove belt pulleys and clutches heat generation and cover them with a touch guard Impermissible belt tensions must be avoided technical list The machines are half key balanced The...

Страница 5: ...L2 L3 can exceed and destroy the input current limit In case of cyclic mains switching over a longer period of time three minutes have to pass between two starting operations Depending on the controll...

Страница 6: ...or monitoring are saved in codes under the menus User and all The codes have numbers 6 and are abbreviated in the text with a C before the number Some codes store the parameters in numerical subcodes...

Страница 7: ...8 0 5 V 0 10 V 0 20 mA C0034 Setpoint selection range 0 Application I O X3 1U 0 5 V 0 10 V X3 2U 0 5 V 0 10 V C0007 Fixed configuration of digital inputs 0 E4 E3 E2 E1 C0007 Fixed configuration of dig...

Страница 8: ...p q r Hi Hz Lo 1 j g f k i h PS 0988 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0001 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0007 ALL 000 000 a b c d e m n op q r Hi Hz Lo 1...

Страница 9: ...other are assigned to the same signal source Correct configuration in C0410 Use internal voltage source X3 20 for function modules Standard I O INTERBUS PROFIBUS DP or LECOM B RS485 Bridge between X3...

Страница 10: ...transmitter Increase monitoring time under C0357 3 if necessary ce4 a 65 BUS OFF many communication errors occurred Controller has received too many faulty telegrams via system bus and has been disco...

Страница 11: ...rings OH3 a 53 PTC monitoring TRIP only generated if C0119 1 4 Motor too hot because of impermissibly high current or frequent and long acceleration processes Check drive selection a y g or 4 PTC not...

Страница 12: ...ult Keypad PC 1 rSt a 76 Faulty auto TRIP reset More than 8 fault messages in 10 minutes Depends on the fault message sd5 a 85 Open wire at analog input setpoint range 4 20 mA Current at analog input...

Отзывы: