Information for the operator

of the machine/system

EDK82MVXXX

!N;,

Global Drive

8200 motec

Frequency inverter

0.25 ... 7.5 kW

Ä!N;,ä

efesotomasyon.com - Lenze

Show/Hide Bookmarks

Содержание E82MV Series

Страница 1: ...Information for the operator of the machine system EDK82MVXXX N Global Drive 8200 motec Frequency inverter 0 25 7 5 kW N efesotomasyon com Lenze Show Hide Bookmarks...

Страница 2: ...o not change the content you are allowed to use the information in this documentation for your purposes without contacting Lenze The information necessary for the project planning of a machine system...

Страница 3: ...50178 apply 4 Installation The controllers must be installed and cooled according to the regulations given in the corresponding Instructions Ensure careful handling and avoid mechanical overload Do n...

Страница 4: ...tools to mount or remove belt pulleys and clutches heat generation and cover them with a touch guard Impermissible belt tensions must be avoided technical list The machines are half key balanced The...

Страница 5: ...L2 L3 can exceed and destroy the input current limit In case of cyclic mains switching over a longer period of time three minutes have to pass between two starting operations Depending on the controll...

Страница 6: ...or monitoring are saved in codes under the menus User and all The codes have numbers 6 and are abbreviated in the text with a C before the number Some codes store the parameters in numerical subcodes...

Страница 7: ...8 0 5 V 0 10 V 0 20 mA C0034 Setpoint selection range 0 Application I O X3 1U 0 5 V 0 10 V X3 2U 0 5 V 0 10 V C0007 Fixed configuration of digital inputs 0 E4 E3 E2 E1 C0007 Fixed configuration of dig...

Страница 8: ...p q r Hi Hz Lo 1 j g f k i h PS 0988 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0001 000 000 a b c d e m n op q r Hi Hz Lo 1 j g f k i h PS 0007 ALL 000 000 a b c d e m n op q r Hi Hz Lo 1...

Страница 9: ...other are assigned to the same signal source Correct configuration in C0410 Use internal voltage source X3 20 for function modules Standard I O INTERBUS PROFIBUS DP or LECOM B RS485 Bridge between X3...

Страница 10: ...transmitter Increase monitoring time under C0357 3 if necessary ce4 a 65 BUS OFF many communication errors occurred Controller has received too many faulty telegrams via system bus and has been disco...

Страница 11: ...rings OH3 a 53 PTC monitoring TRIP only generated if C0119 1 4 Motor too hot because of impermissibly high current or frequent and long acceleration processes Check drive selection a y g or 4 PTC not...

Страница 12: ...ult Keypad PC 1 rSt a 76 Faulty auto TRIP reset More than 8 fault messages in 10 minutes Depends on the fault message sd5 a 85 Open wire at analog input setpoint range 4 20 mA Current at analog input...