10
UL_Warn_c300_EN
Lenze ¯ MA_c300 ¯ 8.0
Approval (only standard version/without PROFINET)
Underwriter Laboratories (UL), UL 61010−2−201 and CSA C22.2 No. 61010−2−201 (UL File
Number E236341)
Ratings
Standard
PROFINET (opt.)
Input 24 V DC (±25 %), max. current
1.0 A
? A
Output 5 V DC, max. current for modules of the
I/O−System 1000:
0.65 A
0.65 A
Max. surrounding air temperature at relative humidity 10 ... 95 %
Vertical mounting position
55 °C
50 °C
J
Warnings!
Field Wiring Markings
Wiring terminal: Voltage supply (24 V DC)
ƒ
Use 75 °C copper wire only.
ƒ
AWG 22 ... 14 (0.5 ... 2.5 mm
2
), for UL 508A min. AWG 14 (2.5 mm
2
)
ƒ
Torque 5 ... 7 lb−in (0.5 ... 0.6 Nm)
Device
ƒ
For use in a pollution degree 2.
ƒ
This device is classified as ’Open Equipment’, intended for installation
inside control cabinets/panels or machine enclosures (altitude up to
2000 m, min. surrounding air temperature 0 °C).
ƒ
Use only PELV power supply.
ƒ
Use this device only in the manner described in this manual. If the
equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Fieldbus interfaces / Optional filedbus module (MC−Card)
ƒ
Use only together with appropriate cable connectors, provided with screws
for securement and secure connector to avoid loosening.