Parameter setting
Parameter setting with the XT EMZ9371BC keypad
Loading a parameter set
19
EDKVF93−05 EN 2.0
3.1.5
Loading a parameter set
The keypad serves to load a saved parameter set into the main memory when the controller
is inhibited. After the controller is enabled, it operates with the new parameters.
Danger!
ƒ
When a new parameter set is loaded, the controller is reinitialised and acts
as if it had been connected to the mains:
– System configurations and terminal assignments can be changed. Make
sure that your wiring and drive configuration comply with the settings of
the parameter set.
ƒ
Only use terminal X5/28 as source for the controller inhibit! Otherwise the
drive may start in an uncontrolled way when switching over to another
parameter set.
Note!
ƒ
After switching on the supply voltage, the controller always loads parameter
set 1 into the main memory.
ƒ
It is also possible to load other parameter sets into the main memory via the
digital inputs or bus commands.
Step
Key
sequence
Action
1.
Inhibit controller
Terminal X5/28 = LOW
2.
Load the saved parameter set into the
main memory
A
! "
Select the code C0002 "PAR LOAD" in the menu
"Load/Store"
B
Change to the parameter level
The active parameter set is displayed, e. g. display "0"
and "Load Default"
If you want to restore the delivery status, proceed with
D
Select the parameter set to be
loaded
C
Load parameter set 1:
ð
Set "1" "Load PS1"
Load parameter set 2:
ð
Set "2" "Load PS2"
Load parameter set 3:
ð
Set "3" "Load PS3"
Load parameter set 4:
ð
Set "4" "Load PS4"
D
"RDY" goes off. The parameter set is loaded completely
into the main memory if "RDY" is displayed again.
3.
Change to the code level
A
Display of the operating level
B
Display of C0002 "PAR LOAD"
4.
Enable controller
Terminal X5/28 = HIGH
The drive is running with the settings of the loaded
parameter set