Technical data
l
17
EDS84DPSO01 EN 2.1
3.3
Technical data
Supply
The safe input and the output are isolated and designed for a low−voltage supply through
a safely separated power supply unit (SELV/PELV) of 24 V DC. P/N switching input signals
and test pulses
£
1 ms are permissible.
Active sensors are directly connected to the X61 circular connector.
Passive sensors are connected to the X61 circular connector via a switching device. The
switching device must comply with the required performance level of the application.
There is no monitoring for short circuits.
Detailed features of the inputs and outputs of the safety unit
Terminal
Specification
[Unit]
min.
typ.
max.
SIA, SIB
Low signal
V
−3
0
5
High signal
V
18
24
30
Input capacitance at switch−off
nF
3
Input delay (tolerated test pulse)
ms
1
Switch−off time (depending on the controller)
ms
2.5
4
Running time
ms
3
Input current
mA
45
50
Input capacitance at switch−on, reduced
m
F
22
GI
GND potential for SIA / SIB and for the non−safe
signalling output
24O
Supply voltage through safely separated power supply
unit (SELV/PELV)
V
18
24
30
DO
Low signal
V
0
0.8
High signal
V
18
24
30
24O, DO
Output current
A
0.2
Truth table
Safe input / channel
Signalling
output
Controller
SIA
SIB
DO1/DO
Description of device status
Enable
0
0
1
"Safe torque off" activated
0
0
1
0
0
1
0
0
0
1
1
0
Drive active
1
)
Note!
Safe inputs have two channels (...A/...B). The channels must be triggered
separately and simultaneously (equivalent).
Active triggering of only one channel indicates faulty sensors or impermissible
wiring.
Despite this, the integrated safety system is activated as soon as at least one
channel has been triggered.