Extensions for automation
Modules
Mounting and dismounting function modules
129
EDK82EV222 DE/EN/FR 13.0
Mounting and dismounting function modules
Danger!
Dangerous electrical voltage
Terminals can carry dangerous electrical voltage − also if the motor is stopped or after
the mains is switched off!
Possible consequences:
ƒ
Death or severe injuries when touching live terminals.
Protective measures:
Before all operations on the controller
ƒ
Switch off the mains voltage and wait for at least 3 minutes.
ƒ
Check whether terminals are isolated from supply, since
–
the power terminals U, V, W, +UG, −UG, BR1, BR2, and the pins of the FIF interfaces
still carry dangerous voltage for at least 3 minutes after power−off.
–
the power terminals L1, L2, L3; U, V, W, +UG, −UG, BR1, BR2, and the pins of the FIF
interfaces carry dangerous voltage when the motor is stopped.
–
the relay outputs K11, K12, K14 can carry dangerous voltage when the drive
controller is disconnected from the mains.