![Lenze 1.5 24 A Series Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/lenze/1-5-24-a-series/1-5-24-a-series_mounting-instructions_1882251037.webp)
Technical data
Rated data
l
37
EDKZN3B024 DE/EN/FR 3.0
4.2
Rated data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
3/PE AC
480
432 − 0 % ... 528 + 0 %
45 − 0 % ... 65 + 0 %
Type
Voltage
Frequency
Current [A]
Number
of phases
[V]
[Hz]
up to +40 °C
up to +55 °C
EZN3x2400H002
400/480
50/60
1.5
0.9
3
EZN3x1500H003
400/480
50/60
2.5
1.6
3
EZN3x0900H004
400/480
50/60
4.0
2.5
3
EZN3x0750H005
400/480
50/60
5.0
3.1
3
EZN3x0500H007
400/480
50/60
7.0
4.4
3
EZN3x0400H009
400/480
50/60
9.0
5.6
3
EZN3x0300H013
400/480
50/60
13.0
8.1
3
EZN3x0250H015
400/480
50/60
15.0
9.4
3
EZN3x0150H024
400/480
50/60
24.0
15.0
3
Temperature in the control cabinet
Power loss
Inductance
Voltage drop
P
loss
[W]
L [mH]
D
U [V]
EZN3x2400H002
17
24
20
EZN3x1500H003
18
15
20
EZN3x0900H004
28
9.0
20
EZN3x0750H005
32
7.5
20
EZN3x0500H007
39
5.0
20
EZN3x0400H009
49
4.0
20
EZN3x0300H013
53
3.0
20
EZN3x0250H015
75
2.5
20
EZN3x0150H024
90
1.5
20