Safety instructions
Residual hazards
l
30
EDKZN3B024 DE/EN/FR 3.0
2.2
Residual hazards
{
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ
Death or severe injuries when touching the power terminals.
Protective measures:
ƒ
Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ
Make sure that all power terminals are deenergised.
{
Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ
Death or severe injuries when touching the device in the event of
an error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ
Fixed installation
– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section
³
10 mm
2
.
ƒ
Connection with a connector for industrial applications according
to IEC 60309 (CEE):
– PE conductor cross−section
³
2.5 mm
2
as part of a multi−core
supply cable.
– Provide for suitable strain relief.