System x3650 M5
46
Physical and electrical specifications
Dimensions and weight (approximate):
Height: 86.5 mm (3.4 in.)
Width: 445.6 mm (17.5 in.)
Depth: 800 mm (31.5 in.)
Weight:
Minimum configuration: 19 kg (42 lb)
Maximum configuration: 34 kg (75 lb)
Supported environment:
Air temperature:
Server on: 5 °C to 40 °C (41 °F to 104 °F); altitude: 0 to 950 m (3,117 ft); decrease the maximum
system temperature by 1 °C for every 175-m increase in altitude above 950 m.
Server off: 5 °C to 45 °C (41 °F to 113 °F)
Maximum altitude: 3,050 m (10,000 ft), 5 °C to 28 °C (41 °F to 82 °F)
Shipment: -40 °C to +60 °C (-40 °F to 140 °F) at up to 10,700 m (35,105 ft)
Humidity:
Server on: 8% to 85%, maximum dew point 24 °C, maximum rate of change 5 °C/hr
Server off: 8% to 85%, maximum dew point 27 °C
Design to ASHRAE Class A3, ambient of 36 °C to 40 °C (96.8 °F to 104 °F), with relaxed support:
Supports cloud-like workload with no performance degradation acceptable (Turbo-Off).
Under no circumstance can any combination of worst-case workload and configuration result in
system shutdown or design exposure at 40 °C.
The worst-case workload (like Linpack, Turbo-On) might have performance degradation.
Electrical:
Models with 1500 W Platinum power supplies:
200 - 240 (nominal) V ac; 50 Hz or 60 Hz; 8.35 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.15 kVA
Maximum configuration: 1.967 kVA
Models with 1300 W Titanium power supplies:
200 - 240 (nominal) V ac; 50 Hz or 60 Hz; 7.137 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.15 kVA
Maximum configuration: 1.700 kVA
Models with 900 W AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 10.3 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 5.0 A
Input kilovolt-amperes (kVA) (approximately):
Minimum configuration: 0.15 kVA
Maximum configuration: 1.194 kVA