• The release pin
1
secures the system board in place.
Figure 154. System board installation
After installing the system board:
1. Install any components that you removed from the failing system board. See the related topics in
Chapter 3 “Hardware replacement procedures” on page 89.
2. Push the power supplies into the bays until they click into place.
3. Complete the parts replacement. See “Complete the parts replacement” on page 203.
4. Update the Universal Unique Identifier (UUID). See “Update the Universal Unique Identifier (UUID)” on
5. Update the SMBIOS/DMI information. See “Update the DMI/SMBIOS data” on page 198.
6. Enable TPM/TCM. See “Enable TPM/TCM” on page 200.
7. Optionally, enable Secure Boot.
Update the Universal Unique Identifier (UUID)
The Universal Unique Identifier (UUID) must be updated when the system board is replaced. Use the Lenovo
XClarity Essentials OneCLI to update the UUID in the UEFI-based solution. Lenovo XClarity Essentials
OneCLI is an online tool that supports several operating systems; make sure that you download the version
for your operating system.
Notes:
You can use Lenovo XClarity Provisioning Manager to update the UUID for the solution:
1. Start the solution and press F1 to display the Lenovo XClarity Provisioning Manager system setup
interface.
2. From the System Summary page, click
Update VPD
.
3. Update the UUID.
To download Lenovo XClarity Essentials OneCLI, go to the following site:
https://datacentersupport.lenovo.com/solutions/HT116433
Lenovo XClarity Essentials OneCLI sets the UUID in the Lenovo XClarity Controller. Select one of the
following methods to access the Lenovo XClarity Controller and set the UUID:
196
ThinkSystem SR650 Maintenance Manual
Содержание ThinkSystem SR650
Страница 1: ...ThinkSystem SR650 Maintenance Manual Machine Types 7X05 and 7X06 ...
Страница 8: ...vi ThinkSystem SR650 Maintenance Manual ...
Страница 20: ...12 ThinkSystem SR650 Maintenance Manual ...
Страница 96: ...88 ThinkSystem SR650 Maintenance Manual ...
Страница 154: ...Figure 107 Riser 1 assembly removal 146 ThinkSystem SR650 Maintenance Manual ...
Страница 157: ...Figure 111 Installing the screws to secure the riser card Chapter 3 Hardware replacement procedures 149 ...
Страница 212: ...204 ThinkSystem SR650 Maintenance Manual ...
Страница 230: ...222 ThinkSystem SR650 Maintenance Manual ...
Страница 234: ...226 ThinkSystem SR650 Maintenance Manual ...
Страница 243: ......
Страница 244: ......