Chapter 3. Rack cabinet setup
Follow instructions in this topic to setup the rack cabinet.
CAUTION:
The raised floor or slab on which the system will be installed must be capable of supporting the
system's weight. Contact the raised floor tile manufacturer, a structural engineer, or both to verify that
the complete raised floor structure and sub-floor are safe to support the concentrated and distributed
load of the racks and its contents. The evaluation of the slab and any raised floor structure should
consider both the static weight of the rack and its contents, but also the installed weight with any
additional infrastructure such as racks attached cable trays, additional cables, Rear Door Heat
Exchangers, containment structures that rest on the racks, personnel in the space, etc… Depending
on the type of raised floor tile, additional supports, such as pedestals or custom support frames,
might be necessary to maintain the structural integrity of an uncut tile or to restore the integrity of a
tile that is cut for cable or hose entry/exit. Contact the raised floor tile manufacturer, a structural
engineer, or both to ensure that the raised floor tiles and pedestals can support the concentrated
loads.
Special consideration should be given to the dynamic/rolling weight of the rack and its contents to
ensure the integrity of the raised floor or slab is not compromised when rolling loaded racks across
the floor. In some cases, load distribution plates may be required to better distribute the dynamic load
of a rolling rack at various points from the loading dock to the data center and on to the data center
floor. Other things to consider are ramps, lifts/elevator ratings, hallways, transitions between different
types of flooring or sub-floors, elevation differences between floors, gaps between elevator entry
points and the main floors.
Space planning
Follow the guidelines in this topic to make plans for the space that will contain the rack cabinet.
See the following illustration for distances between various components on the bottom of the rack cabinet,
and make plans accordingly.
© Copyright Lenovo 2021
13
Содержание ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet
Страница 1: ...ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide Machine Type 7D6D ...
Страница 4: ...ii ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Страница 16: ...12 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Страница 23: ...Figure 19 Rising the leveling pads Chapter 3 Rack cabinet setup 19 ...
Страница 145: ...Figure 159 Installing a rear cable management bracket Chapter 5 Hardware removal installation and reversion 141 ...
Страница 146: ...142 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Страница 152: ...148 ThinkSystem Heavy Duty Full Depth 42U Rack Cabinet User Guide ...
Страница 153: ......
Страница 154: ......