ThinkStation Static Rail Kit 

 http://www.lenovo.com/support

 

 

PN: SP40K32881 

Printed in China

 

 

 

 

Important information about the ThinkStation 

Static Rail Kit 

This document provides important information about the ThinkStation Static Rail Kit.  

If you want to install a ThinkStation

®

 computer into a rack, you need one set of rails. The 

set of rails is designed for fixing a 4U ThinkStation computer into a rack without the 

flexibility of sliding in or out. (“U” is the unit of measurement for defining the vertical space 

used by your ThinkStation computer and 1U is equivalent to 4.445 cm or 1.75 inches.) 
Your rail kit package contains: 

  One set of rails 

  Two locking clips 

  One stopper 

  Two cage nuts 

  Two bolts 

  Documentation 

If any item is missing or damaged, contact your place of purchase. Ensure that you retain 

your proof of purchase and packing material. They might be required to receive warranty 

service. 

About the rack 

CAUTION: Be sure to read and understand the documentation that comes with the 

rack for safety and cabling information. Before you install a workstation into the 

rack, also ensure that you read and understand all safety information and 

guidelines in this document. Reading and understanding the information reduces 

the risk of personal injury and damage to your product. 

The rack must meet one of the following requirements: 

  Standard 4-post (square-hole), 19-inch rack configuration compliant with EIA-310-E 

as defined by the Electronic Industries Alliance 

  Standard 4-post (unthreaded round-hole), 19-inch rack configuration compliant with 

EIA-310-E as defined by the Electronic Industries Alliance 

The dimensions of the rack must meet the following requirements: 

 

  Rear mounting flange 
  Front mounting flange 
  Rack front door 

The following table explains the dimension requirements of the rack. 

Item 

Dimensions 

Description 

609.6 – 914.4 mm 

(24 – 36 inches) 

Item A refers to the distance between the front 

mounting flange   and the rear mounting flange  . 

The distance must be 609.6 mm (24 inches) in 

minimum and 914.4 mm (36 inches) in maximum. 

> 474 mm  
(18.66 inches) 

Item B refers to the internal width of the rail kit. The 

width must exceed 474 mm (18.66 inches). 

> 60 mm  
(2.36 inches) 

Item D refers to the distance between the front 

mounting flange   and the inside of the rack front 

door  . The distance must exceed 60 mm (2.36 

inches). This clearance is required for the chassis pull 

handles on the front of the ThinkStation computer as 

well as air circulation through the rack. 

> 950 mm  
(37.4 inches) 

Item L refers to the distance between the front 

mounting flange   and the rear of the rack. The 

distance must exceed 950 mm (37.4 inches).  

Read these guidelines first 

Before you install the ThinkStation computer into a rack, review the following guidelines. 

The guidelines help you in your installation and avoid the risk of personal injury and 

damage to your product. 
Two or more people are required to lift a ThinkStation computer, move a ThinkStation 

computer, or install a ThinkStation computer into a rack. You also can use a workstation 

computer-lifting tool for help.  

 

 

 

 

 

≥ 18 kg (39.7 lb)

 

< 32 kg (70.5 lb)

 

 

32 kg (70.5 lb)

 

< 55 kg (121.2 lb)

 

≥ 55 kg (121.2 lb)

 

< 100 kg (220.5 lb)

 

CAUTION 
       Use safe practices when lifting. 

  Before installing a ThinkStation computer into a rack, remove all media from the 

drives and turn off all attached devices and the ThinkStation computer. Then, 

disconnect all power cords from electrical outlets and disconnect all cables that are 

connected to the ThinkStation computer. 

  Ensure that the room air temperature is below 35°C (95°F). 

  Do not block any air vents; usually 15 cm (6 inches) of space provides proper airflow. 

  Do not leave open spaces above or below an installed ThinkStation computer in your 

rack. To help prevent damage to ThinkStation computer components, always install a 

blank filler panel to cover the open space and to help ensure proper air circulation. 

  Install the ThinkStation computer only in a rack with perforated doors for both security 

and proper airflow. 

  Start from the bottom of the rack for the ThinkStation computer or device installation. 

  Install the heaviest ThinkStation computer or device in the bottom of the rack. 

  Do not extend more than one ThinkStation computer or device out of the rack at the 

same time. 

  If possible, remove the doors and side panels of the rack to provide easier access 

during installation. 

  Do not overload the electrical outlet when you install multiple devices in the rack. 

  Connect all power cords to proper electrical outlets and properly manage all the 

cables in the rack. Refer to the documentation that comes with the rack about 

managing cables. 

  Do not place any object on top of rack-mounted devices. 

  When you move or ship the rack, remove the ThinkStation computer secured by the 

rail kit from the rack first. Refer to the documentation that comes with the rack and the 

documentation that comes with each rail kit for detailed information. 

Installing a ThinkStation computer into a rack 

(with static rail kit) 

Before you begin, remove all the parts from the rail kit package and lay all the parts on a 

working surface. Measure the rack before the installation to ensure that the rack can 

accommodate the static rail. 

Note:

 The holes in a mounting flange are separated into groups by measuring marks. The 

three holes between two adjacent measuring marks form a group, which indicates 1U 

space. Note the measuring marks on a mounting flange to help you correctly select a rack 

mounting area for the ThinkStation computer. For more information about the placement 

of the holes in a mounting flange, refer to the documentation that comes with the rack. 
To install a ThinkStation computer into a rack, do the following: 
1.  Install the rail kit by doing the following: 

a.  Select a proper rack mounting area for the left static rail. Position the rear end of 

the left rail to the mounting area. Ensure that the tabs on the rear end of the rail 

are aligned with the corresponding holes in the mounting area. Press the latch   

and push the rail until the rear end of the left static rail is firmly secured to the 

mounting flange. 
If the holes in a mounting flange are round, the installation method is the same. 

Press the latch   and push the rail until the inner round posts of the tabs are 

inserted into the corresponding holes. Then, the rear end of the rail is firmly 

secured to the mounting flange. 

 

b.  Position

 

the front end of the left static rail to the mounting flange. Ensure that the 

front end and rear end of the left static rail are at the same horizontal level. Press 

the latch   and push the rail until the front end of the rail is firmly secured to the 

mounting flange.  
If the holes in a mounting flange are round, the installation method is the same. 

Press the latch   and push the rail until the inner round posts of the tabs are 

inserted into the corresponding holes. Then, the front end of the rail is firmly 

secured to the mounting flange. 

 

c.  Repeat steps a through b to install the right static rail to the opposite side of the 

rack. 

2.  Depending on the type of the handles on the front of your computer, install a locking 

clip or two cage nuts on the front mounting flange. 

  For the computer handle with a hole, install a locking clip. Remove the two screws 

on the side of the locking clip. Install the locking clip on the mounting flange 

above the rail as shown. Then reinstall the two screws to secure the locking clip 

to the mounting flange. 

  For the computer handle without a hole, install the two cage nuts on the mounting 

flange above the rail as shown. 

 

3.  Remove the four feet on the bottom of the computer. 

 

4.  Position the computer onto the rails. Then slide the computer to the rear of the rack 

until the hole in the computer handle is aligned with the locking clip. 

 

5.  Secure the computer to the rack by either of the following: 

  Press the button on each locking clip. 

 

  Press the button on the locking clip  . Align the holes in the stopper with the 

installed cage nuts and position the stopper onto the computer handle. Install the 

two bolts to secure the stopper on the mounting flange  . 

 

Legal notices 

Lenovo

®

, the Lenovo logo, ThinkStation, and the ThinkStation logo are trademarks of 

Lenovo in the United States, other countries, or both. 
Other company, product, or service names may be trademarks or service marks of others.  

 

Содержание 4XF0K29048

Страница 1: ...computer only in a rack with perforated doors for both security and proper airflow Start from the bottom of the rack for the ThinkStation computer or device installation Install the heaviest ThinkStation computer or device in the bottom of the rack Do not extend more than one ThinkStation computer or device out of the rack at the same time If possible remove the doors and side panels of the rack t...

Страница 2: ...um fluxo de ar adequado Comece pela parte de baixo do rack para instalar o computador ThinkStation ou dispositivo Instale o computador ThinkStation ou dispositivo mais pesado na parte inferior do rack Não estenda mais de um computador ThinkStation ou dispositivo para fora do rack ao mesmo tempo Se possível remova as portas e os painéis laterais do rack para facilitar o acesso durante a instalação ...

Страница 3: ...u cirkulaci vzduchu Počítač ThinkStation instalujte pouze do racku s perforovanými dveřmi a to z důvodů bezpečnosti a správného proudění vzduchu Při umísťování počítače ThinkStation nebo jiných zařízení začínejte odspodu racku Dolů umístěte nejtěžší počítač ThinkStation nebo zařízení Nikdy z racku nevysouvejte více než jeden počítač ThinkStation nebo jiné zařízení současně Je li to možné sejměte z...

Страница 4: ...l ordinateur ThinkStation par le bas de l armoire Installez l ordinateur ThinkStation ou le périphérique le plus lourd dans la partie inférieure de l armoire Ne sortez pas de l armoire plusieurs ordinateurs ThinkStation ou périphériques à la fois Retirez si possible les volets et les panneaux latéraux de l armoire pour faciliter l accès lors de l installation Ne surchargez pas la prise de courant ...

Страница 5: ...n Sie den schwersten ThinkStation Computer bzw das schwerste Gerät unten im Rack an Ziehen Sie nie mehrere ThinkStation Computer oder Einheiten gleichzeitig aus dem Rack heraus Entfernen Sie nach Möglichkeit die Türen und die Seitenabdeckungen des Racks um beim Anbringen besseren Zugriff auf die Komponenten zu haben Überlasten Sie nicht die Netzsteckdose wenn Sie mehrere Einheiten im Rack anbringe...

Страница 6: ...tation o del dispositivo dalla parte inferiore del rack Installare il computer ThinkStation o il dispositivo più pesante nella parte inferiore del rack Non estendere più computer ThinkStation o dispositivi contemporaneamente fuori dal rack Se possibile rimuovere le porte e i pannelli laterali del rack per agevolare l accesso durante l installazione Non sovraccaricare la presa elettrica durante l i...

Страница 7: ... 95 F 以下であることを確認します 通気口をふさがないでください 通常 15 cm 6 インチ のスペースがあれば空気が 正しく流れます ラックに ThinkStation コンピューターを搭載する場合は 上下にスペースを残さな いでください スペースが残る場合は ThinkStation コンピューターのコンポーネン トの破損を防止するため換気用のブランク フィラー パネルを取り付けてそのスペ ースを埋めてください ThinkStation コンピューターは セキュリティーおよび適切な換気の両方を確保する ため 穴の開いたカバー付きラックにのみ取り付けます ThinkStation コンピューターまたはデバイスの取り付けは ラックの最下段から開始 します 最も重量のある ThinkStation コンピューターまたはデバイスは ラックの最下段に 取り付けてください ラックから同時に複...

Страница 8: ...zowel voor de veiligheid als voor een goede luchtdoorstroming Begin aan de onderkant van het rek met de installatie van de ThinkStation computer of het apparaat Installeer de zwaarste ThinkStation computer of het zwaarste apparaat onder in het rek Laat niet meer dan één ThinkStation computer of apparaat tegelijkertijd uit het rek steken Verwijder indien mogelijk de toegangsdeuren en zijpanelen van...

Страница 9: ... стойки с перфорированными дверцами которые обеспечивают безопасность и необходимый воздушный поток Установку компьютера ThinkStation или устройства начинайте с нижней части стойки Самый тяжелый компьютер ThinkStation или устройство устанавливайте в нижней части стойки Не выдвигайте из стойки более одного компьютера ThinkStation или устройства одновременно Если это возможно снимите дверцы и боковы...

Страница 10: ...算机装入机架之前 请从驱动器中取出所有介质 关闭所有连接的 设备和 ThinkStation 计算机 然后从电源插座中拔出所有电源线 并拔下连接到 ThinkStation 计算机的所有线缆 请确保室内空气温度在 35 C 95 F 以下 请勿挡住任何通风孔 通常情况下 留出 15 厘米 6 英寸 的空间可确保空气正常流通 请勿在安装于机架中的 ThinkStation 计算机上下留出开放空间 为帮助防止 ThinkStation 计算机组件损坏 请始终安装空白填充面板以填充开放空间并帮助确保空 气正常流通 只能将 ThinkStation 计算机安装在挡板穿孔的机架中以确保安全和空气正常流通 从机架底部开始安装 ThinkStation 计算机或设备 将最重的 ThinkStation 计算机或设备装入机架底部 请勿同时让多个 ThinkStation 计算机或设备伸出机架 如有可能 请...

Страница 11: ... len do stojana s perforovanými dvierkami z dôvodu bezpečnosti a primeraného prúdenia vzduchu Inštaláciu počítača alebo zariadenia ThinkStation začnite zospodu stojana Najťažší počítač alebo zariadenie ThinkStation nainštalujte do spodnej časti stojana Nerozširujte súčasne viac ako jeden počítač alebo zariadenie ThinkStation mimo stojana Ak je to možné odmontujte dvierka a bočné panely stojana aby...

Страница 12: ...rforadas para brindar seguridad y un flujo de aire adecuado Para la instalación del equipo ThinkStation o dispositivo empiece desde la parte inferior del bastidor Instale el equipo ThinkStation o dispositivo más pesado en la parte inferior del bastidor No extienda más de un equipo ThinkStation o dispositivo fuera del bastidor al mismo tiempo Si es posible extraiga las puertas y paneles laterales d...

Страница 13: ...使用安全做法 將 ThinkStation 電腦裝入機架之前 請從磁碟機中取出所有媒體 然後關閉所有連接 裝置和 ThinkStation 電腦 接著拔下電源插座上的所有電源線 以及拔掉所有連接到 ThinkStation 電腦的纜線 請確定室溫低於 35 C 95 F 請勿擋住任何通風孔 通常情況下 保留 15 公分 6 吋 的空間即可確保適當的空氣 流通 請勿在機架中安裝的 ThinkStation 電腦上方或下方保留開放空間 為了協助防止 ThinkStation 電腦元件損壞 請一律安裝空白充填面板以覆蓋開放空間 並協助確保有 適當的空氣循環 只能將 ThinkStation 電腦安裝在門板穿孔的機架中 以確保安全和適當的空氣流通 從機架底部開始安裝 ThinkStation 電腦或裝置 將最重的 ThinkStation 電腦或裝置安裝在機架底部 請勿同時將多部 ThinkSta...

Страница 14: ...osu takın ThinkStation bilgisayarını hem güvenlik hem de uygun bir hava akışı sağlamak amacıyla sadece delikli kapakları olan bir rafa kurun ThinkStation bilgisayarı veya cihaz kurulumu işlemine rafın en altından başlayın En ağır ThinkStation bilgisayarını veya cihazı rafın en altına kurun Aynı anda birden fazla ThinkStation bilgisayarının veya cihazın rafın dışına sarkmasına izin vermeyin Mümküns...

Отзывы: