31
Technical Information
Service Manual
(12) Starting-up Failure Protection for Compressor
Stop the compressor after its starting-up fails, restart it after 20s if the fault doesn’t shows, and if they are all failing for the successive start
3 times, it shall be reported as Starting-up Failure, and then restart up it after 3 min. When it still not be able to operate through carry out the
above process for 5 times, it is available if press ON/OFF. And the compressor should be cleared the times after it run 2 min.
(13) Out-of-Step Protection for Compressor
The out-of-step protection signal should be detected immediately after starting-up compressor, and once find the out-of-step protection signal,
the out-of-step protection shall be stopped; if it can run for lasting power turn-off 3 min, the machine shall be allowed to operate. If it still can’t
run automatically when the out-of-step protection for compressor happens to stop working for 6 times in succession, it needs to press ON/OFF
to operate. And if the running time is more than 10 min, the power turn-off times for out-of-step protection shall be cleared and recounted.
(14) Voltage Abnormity Protection for DC Bus
To detect voltage abnormity protection for dc bus after completing the pre-charge:
1.Over-High Voltage Protection for DC Bus:
If it found the DCbus voltage U
DC
>[U
DC Jiekuangchun Protection
], turn off PFC and stop the compressor at once, and it shall show the DC over-high
voltage failure; it should clear out the failure when the voltage dropped to U
DC
<[U
DC Jiekuangchun Recovery
] and the compressor stopped for 3 min.
2.Over-Low Voltage Protection for DC Bus:
If it found the DC bus voltage U
DC
<[U
DC Wantuochun Protection
], turn off PFC and stop the compressor at once, and it shall show the DC over-low
voltage; and it should clear out the failure when the voltage raised to U
DC
>[U
DC Wantuochun Recovery
] and the compressor stopped for 3 min.
3.To detect voltage abnormity protect for DC bus when getting electricity:
If it found the DC bus voltage U
DC
>[U
DC—Over-High Voltage
], turn off the relay at once, and shows voltage abnormity failure for DC Bus. And the failure
can’t recover except to break off and get the electricity.
(15)Abnormity Protection for Four-way Valve
Under the model of heating operation in good condition: the compressor is detected [T
Inner Tube
<(T
Inner Ring
-T
Abnormity Temperature Difference For Four-Way Valve
Reversion
)], during the running, it should be regarded as four-way valve reversion abnormity. And then it can run if stop the reversion abnormity
protection for four-way valve 3 min; and if it still can’t run when the reversion abnormity protection for four-way valve happens to stop working
for 3 times in succession, it is available if presses ON/OFF.
Attention: the protection shall be shielded during the testing mode and defrosting process, and it shall be cleared out the failure and its times
immediately when turning off or delivering wind / cooling / dehumidifying mode conversed (the inverted mode don’t clear out the failure when it
can’t recover to operate).
(16) PFC Protection
1. After start up the PFC, it should detect the protection signal of PFC immediately; under the condition of PFC protection, it should turn off the
PFC and compressor at one time;
2. It shows the failure is cleared out if PFC Protection stopped working 3 min and recovers to run automatically;
3. If it still can’t run when it occurs PFC protection for 3 times in succession, it is available if presses ON/OFF; and clear the PFC Protection
times when start up PFC for 10min.
(17) Failure Detection for Sensor
1. Outdoor Ambient Sensor: detect the failure of sensor at all times.
2. Outdoor Tube Sensor: You should not detect the failure of outdoor tube sensor within 10 minutes heating operation compressor except the
defrosting, and you could detect it at other time.
3. Outdoor Exhaust Sensor:
(a) The compressor only detect the sensor failure after it start up 3 min in normal mode;
(b) It should detect the exhaust sensor failure immediately in the testing mode.
4. Module Temperature Sensor:
(a) Short-Circuit Detection: the compressor should be detected immediately when the module temperature sensor occurs short-circuits;
(b) Open-Circuit Detection: the compressor should be detected on open-circuit when it runs 3min (it needn’t 30s avoiding the module over-
heated).
(c) Detect the sensor failure at all times in the testing mode.
5. Disposal for Sensor Protection
(1) When the short-circuit of sensor is detected within 30s, It is regarded as the temperature of sensor over-high (or infinitely high), and now
according to the over-high sensor, the machine should carry out the corresponding protection to stop working, and show the corresponding
temperature shutdown protection and sensor failure at the same time (for example: the compressor stops immediately when the outdoor tube
sensor short-circuit, and the machine shall show the overload protection and outdoor tube sensor failure).
(2) When the open-circuit of sensor is detected within 30s, The protection shall be stopped and it shall show the corresponding sensor failure.
Содержание Y6334
Страница 83: ...80 Installation and Maintenance Service Manual...