Page 25
XPG15 SERIES
System Setup Information
COMFORTSENSE
7000 SETUP SELECTIONS (CATALOG# Y0349)
Checked
TAB MENU ITEM
PARAMETER
SELECTION DESCRIPTION
OPTIONS
INSTALLER
SETTINGS
SYSTEM SETUP
HEAT PUMP / ELECTRIC
COMPRESSOR STAGES
1
INDOOR HEAT STAGES
4
1 OR 2
1
OUTDOOR SENSOR (OA)
2
NO
OA – LOW BALANCE POINT
3
OFF
OFF (Use down arrow to go one step below lowest set point.)
OA – HIGH BALANCE POINT
3
1
Select 1 or 2 to match number of furnace heat stages
2
Outdoor sensor can be used in the display ONLY mode by setting
OUTDOOR SENSOR
to
YES
and the
LOW
and
HIGH
balance point to
OFF
.
3
If outdoor sensor is not present and user tries to select the options DISPLAY INFO −> OUTDOOR TEMP, LOW BALANCE POINT, HIGH
BALANCE POINT, DEW POINT CONTROL or HUMIDITROL, OUTDOOR SENSOR REQUIRED" message is displayed instead of scroll options
for these menus.
4
Confirm temperature differential setting for first and second stages. Factory defaults are 1ºF. See ComfortSense
®
7000
Installation instructions for
procedures on how to confirm temperature differential settings.
COMFORTSENSE
5000 SETUP SELECTIONS (CATALOG# X4147)
Checked
INSTALLER
SETUP #
INSTALLER SETUP NAME
SELECT
0170
SYSTEM TYPE *
7
– Two Heat/One Cool Heat Pump – Heat pump with
auxiliary or back−up heat.
0200
AUXILIARY HEAT SOURCE**
0
– Electric Heat is used as auxiliary heat source in heat
pump application. (Factory setting)
(DO NOT USE FOSSIL FUEL SETTING)
0340
REMOTE OUTDOOR TEMPERATURE
SENSOR
0
– No remote outdoor temperature sensor.
or
1
– Outdoor temperature sensor used for display ONLY
* Use
W2
staged time feature for two−stage furnaces with ComfortSense
®
5000.
** Confirm cycle per hour rate settings per stage settings. See ComfortSense
®
5000
Installation instructions for procedures on how to confirm cycle
rate.
IMPORTANT
Do not use
Y2
for furnace gas heat
FURNACE SETUP SELECTIONS
Checked
Item #
Task
1
Integrated control must allow gas furnace operation with
W and O input
. *
2
Integrated control with the W951 link (link from
R to 0)
must be cut. **
*Integrated control with catalog # 23W25 [and 19W60 after date code 0710 (revision 1.11)] will accept both inputs. See Service and Application Note
H−06−6)
**When W951 link is cut, cooling blower profiles will be disabled in the heat pump heating mode
XPG15 SETUP SELECTIONS
Checked
Item #
Task
1
Verify proper coil sensor location and all demand defrost control jumper pin positions
NOTE Demand defrost control will not output a W out when outdoor temperatures are above 65
5
F (18
5
C).