Page 17

XP21 SERIES

STEP 6 -- INSTALLING INDOOR EXPANSION VALVE 

 A.

ATTACH THE VAPOR LINE SENSING BULB IN THE PROPER
ORIENTATION AS ILLUSTRATED TO THE RIGHT USING THE
CLAMP AND SCREWS PROVIDED.

NOTE

 -

 CONFIRM PROPER THERMAL CONTACT BETWEEN

VAPOR LINE AND CHECK EXPANSION BULB BEFORE INSU­
LATING THE SENSING BULB ONCE INSTALLED.

 B.

CONNECT THE EQUALIZER LINE
FROM THE EXPANSION VALVE TO
THE EQUALIZER VAPOR PORT ON
THE VAPOR LINE. FINGER
TIGHTEN THE FLARE NUT PLUS
1/8 TURN (7 FT-LBS) AS ILLUS­
TRATED BELOW.

THE EXPANSION VALVE UNIT CAN BE INSTALLED INTERNAL OR
EXTERNAL TO THE INDOOR COIL. IN APPLICATIONS WHERE AN
UNCASED COIL IS BEING INSTALLED IN A FIELD-PROVIDED
PLENUM, INSTALL THE CHECK EXPANSION VALVE IN A MANNER
WHICH PROVIDES ACCESS FOR FIELD SERVICING OF THE
EXPANSION VALVE. REFER TO BELOW ILLUSTRATION FOR
REFERENCE DURING INSTALLATION OF EXPANSION VALVE
UNIT.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR
FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

SENSING BULB INSULATION IS REQUIRED
IF MOUNTED EXTERNAL TO THE COIL
CASING. SEE SENSING BULB
INSTALLATION FOR BULB POSITIONING.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

THIS OUTDOOR UNIT IS DESIGNED FOR USE IN SYSTEMS THAT USE A CHECK EXPANSION VALVE METERING DEVICE. SEE THE

 LENNOX XP21

PRODUCT SPECIFICATION

 FOR APPROVED EXPANSION VALVE KIT MATCH-UPS AND APPLICATION INFORMATION.

 A.

REMOVE THE FIELD-PROVIDED FITTING THAT TEMPORARILY RECON­
NECTED THE LIQUID LINE TO THE INDOOR UNIT'S DISTRIBUTOR AS­
SEMBLY.

 B.

INSTALL ONE OF THE PROVIDED TEFLON

®

 RINGS AROUND THE

STUBBED END OF THE EXPANSION VALVE AND LIGHTLY LUBRICATE
THE CONNECTOR THREADS AND EXPOSE SURFACE OF THE TEFLON

®

RING WITH REFRIGERANT OIL.

 C.

ATTACH THE STUBBED END OF THE EXPANSION VALVE TO THE LIQUID
LINE ORIFICE HOUSING. FINGER TIGHTEN AND USE AN APPROPRIATE­
LY SIZED WRENCH TO TURN AN ADDITIONAL 1/2 TURN CLOCKWISE AS
ILLUSTRATED IN THE FIGURE ABOVE, OR 20 FT-LB.

 D.

PLACE THE REMAINING TEFLON

®

 WASHER AROUND THE OTHER END

OF THE EXPANSION VALVE. LIGHTLY LUBRICATE CONNECTOR
THREADS AND EXPOSE SURFACE OF THE TEFLON

®

 RING WITH RE­

FRIGERANT OIL.

 E.

ATTACH THE LIQUID LINE ASSEMBLY TO THE EXPANSION VALVE. FIN­
GER TIGHTEN AND USE AN APPROPRIATELY SIZED WRENCH TO TURN
AN ADDITIONAL 1/2 TURN CLOCKWISE AS ILLUSTRATED IN THE FIGURE
ABOVE OR 20 FT-LB.

VAPOR LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 TURN

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

REMOVE AND DISCARD EITHER THE FLARE SEAL CAP OR FLARE
NUT WITH COPPER FLARE SEAL BONNET FROM THE EQUALIZER
LINE PORT ON THE VAPOR LINE AS ILLUSTRATED IN THE FIGURE
TO THE RIGHT.

ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.

12

BULB

VAPOR LINE

NOTE - NEVER MOUNT

THE SENSING BULB ON

BOTTOM OF LINE.

BULB

BULB

BULB

9 O'CLOCK TO

3 O'CLOCK

1

2

3

4

5

6

7

8

9

10

11

12

1/8 TURN

FIGURE 16

Содержание XP21 Series

Страница 1: ...nd service must be performed by a licensed professional installer or equivalent or service agency CAUTION Before attempting to perform any service or mainte nance turn the electrical power to unit OFF...

Страница 2: ...18 1 2 470 8 203 1 25 4 7 16 113 LIQUID LINE INLET VAPOR LINE INLET ELECTRICAL INLETS BASE WITH ELONGATED LEGS SIDE VIEW ACCESS VIEW DISCHARGE AIR 37 940 024 THRU 036 47 1194 048 AND 060 16 7 8 429 8...

Страница 3: ...nts from dryers water heaters and furnaces should be directed away from the outdoor unit Prolonged exposure to exhaust gases and the chemicals contained within them may cause condensation to form on t...

Страница 4: ...ze barrier at least the same height and width as out door unit Install barrier 24 inches 610 mm from the sides of the unit in the direction of prevailing winds 24 610 WIND BARRIER PREVAILING WINTER WI...

Страница 5: ...efore unit start up to pre vent compressor damage as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take c...

Страница 6: ...wires between the thermostat and the furnace air handler con trol and four wires between the outdoor unit and the furnace air handler control When a thermostat cable with more than four wires is used...

Страница 7: ...E TARGET 40 DEGREE TARGET DEFAULT 55 50 45 40 55 50 45 40 55 50 45 40 55 50 45 40 DEGREE TARGET 100 90 DEGREE TARGET 70 DEGREE TARGET 50 DEGREE TARGET 90F 70F 50F TARGET 90F 70F 50F 90F 70F 50F 100F 9...

Страница 8: ...d up on the fan blade and orifice ring is when the outdoor ambient is below 35 F and the unit is OFF for more than 30 minutes PREVIOUS TERMINATION TEMPERATURE TERMINATION TEMPERATURE FOR NEXT DEFROST...

Страница 9: ...t s o r f e d l l i w n o i t a n i m r e t g n i t t e s 1 J e h t w o l l o f m u m i x a M E T O N r o f d e w o l l a e m i t s e t u n i m 4 1 s i t s o r f e d See table on Page 10 Next defrost...

Страница 10: ...eached the specified defrost termination temperature in less than 14 minutes Termination temperature set on outdoor control is 50 F 70 F 90 F or 100 F Defrost for 14 minute maximum without the coil te...

Страница 11: ...isplay optional 2 R to L connection is required for this model when using the ComfortSense 7000 catalog number Y0349 only Resistor Kit catalog number 47W97 required and ordered separately 3 Air handle...

Страница 12: ...tage operation 5 Cut loop jumper clippable wire Short DS to R for Humiditrol applications This will slow the outdoor unit s fan speed to a specific RPM A wire must be installed between the DS terminal...

Страница 13: ...nox units charged with HFC 410A refrigerant Residual mineral oil can act as an insulator preventing proper heat transfer It can also clog the expansion device and reduce sys tem performance and capaci...

Страница 14: ...oor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVI...

Страница 15: ...itrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refrigerant lines...

Страница 16: ...ater saturated cloths under the valve body to protect the base paint 4FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on th...

Страница 17: ...KIT MATCH UPS AND APPLICATION INFORMATION A REMOVE THE FIELD PROVIDED FITTING THAT TEMPORARILY RECON NECTED THE LIQUID LINE TO THE INDOOR UNIT S DISTRIBUTOR AS SEMBLY B INSTALL ONE OF THE PROVIDED TEF...

Страница 18: ...der of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the lin...

Страница 19: ...ge caused by deep vacuum operation will void warranty OUTDOOR UNIT TO VAPOR SERVICE VALVE TO LIQUID LINE SERVICE VALVE MICRON GAUGE VACUUM PUMP A34000 1 4 SAE TEE WITH SWIVEL COUPLER 500 MANIFOLD GAUG...

Страница 20: ...30 minutes minimum at the deep vacuum level Deep Vacuum Gauge Response and System Conditions FIGURE 19 Triple Evacuation Method The triple evacuation method should only be used when system does not c...

Страница 21: ...ting to the outside coil tub ing The location of the coil sensor is important for proper defrost operation NOTE The heat pump control accurately measures the performance of the system as frost accumul...

Страница 22: ...els must be in place any time the unit is in operation If you are unsure about the filter required for your system call your Lennox dealer for assistance IMPORTANT Sprinklers and soaker hoses should n...

Страница 23: ...unit 3 Check the cleanliness of indoor blower and clean blower if necessary 4 Inspect the indoor coil drain pans and condensate drains for rust debris obstructions leaks or cracks Pour water in pans...

Страница 24: ...ies with Y2 out terminal on the outdoor control 5 Cycle main power ON 6 Allow pressures and temperatures to stabilize before taking any reading may take up to 10 minutes 7 Record all of the readings f...

Страница 25: ...st Stage Expected results during Y2 demand toggle switch ON Y2 Second Stage Compressor Voltage Same Same Amperage Higher Higher Condenser Fan motor Amperage Same or Higher Same or Higher Temperature A...

Страница 26: ...ure Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information o...

Отзывы: